WARNING! Check that the product delivered exactly corresponds to the ordered
Power electrical connections
AT206 / AT206B “Quick installation guide” UK
Description of the data shown on the label
In = nominal current
Imax = maximum rated current
KA = maximum breaking current against short circuit
Hz = frequency
KVA = apparent power (calculated at cos fi 0,8)
KW = active power
HP = horse power
V~ = maximum use voltage of the primaries
Vaux = maximum voltage of the auxiliary circuits
IP = degree of protection against external agents
Kg = approximate weight
Dim = dimensions Height x Width x Depth
Ser.n = serial number
Model = product code
TECHNICAL FEATURES
Nominal voltage battery ..........................................12Vdc
Maximum rated current..........................................250mA
Maximum rated power ................................................ 3W
Operating range...............................................1017VDC
Nominal voltage generator/mains..........100 ÷ 265Vac L-N
Measuring range voltage appearing…………..50 ÷ 450Vac
Frequency range ............................................... 45 65Hz
Degree of protection front board................................ IP65
Degree of protection of switchboard .......................... IP20
Operating temperature................................... -20 +50°C
Storage temperature...................................... -30 +70°C
Maximum rated humidity..........................................90%
Single-phase system 2P (max 5m)
I max min. sec. max sec.
40A 2x 4mm² 2x 6mm²
51A 2x 4mm² 2x 6mm²
72A 2x 6mm² 2x 10mm²
89A 2x 10mm² 2x 16mm²
96A 2x 10mm² 2x 16mm²
Three-phase system 4P (max 5m)
I max min. sec. max. sec.
25A 1x 4mm² 1x 6mm²
32A 1x 6mm² 1x 6mm²
45A 1x 10mm² 1x 10mm²
56A 1x 16mm² 1x 16mm²
60A 1x 16mm² 1x 16mm²
aeration reason =
min. 10cm
the switchboard
available
available
auxiliary battery circuits 12Vdc
F2 = F2A Protection mains contactor
contactor
FCB = F500mA