OUT of the Box Startup – Overview
This document is intended as a quick start guide to get familiarity with keypad
navigation, changing parameters, and setting the A510 drive up for external
start/stop and external potentiometer signal. Please note this document is not
a substitute for the A510 User Manual and it is important that you reference
the A510 user manual before proceeding.
1
Check Nameplate and Connect Input / Output Wiring -
Check the inverter nameplate to insure that the information agrees with your order. Also insure that the power available is rated
appropriately for the drive being used.
Secure the Inverter in
a suitable location
DANGER
Do not apply power until all
connections are correct
and secure, and all
protective covers are in
place.
!
Remove protective covers to access
the power terminal blocks. (Refer to
the A510 User Manual for detailed
instructions.)
MOTOR
T1 T2 T3
INPUT POWER
L1 L2 L3
Appropriate Input
Power
3Ø Induction Motor
STEP
To reverse direction
of motor rotation
swap any two leads
Ground
3Ø Input
NOTE: Properly check the
GROUND CONNECTION
2
Power-up the Inverter, check the Digital Operator
In this step, after the initial power-up you will become familiar with the indications and functions of the Digital Operator.
STEP
KEYS (8) Description
RUN: RUN Inverter in Local Mode
STOP: STOP Inverter
LOC/REM: Switches between Local and Remote operation
DSP/FUN: Switches between available displays
</RESET: Left Shift: Used to change parameters or values, RESET
alarms and faults
ENTER: Used to display the preset value of parameters and to save
changes
Parameters navigation Up, Increase parameters or reference value
Parameters navigation Down, Decrease parameters or reference value
A510 Control Settings (Factory Default)
RUN/STOP Control: Keypad (RUN / STOP key)
SPEED Control: Keypad (Default 5.00 Hz)
See step 5. to change to RUN/STOP to external switch/contact.
See step 6. to change to external potentiometer control.
Press RUN to start the drive or STOP to stop the drive.
Changing Speed Reference
Press ENTER button and use
to change reference.
Press </RESET button to shift cursor to
the left
Press ENTER button to save
LCD Display
Run Status
Indicator
8 button
Membrane Keypad
Stop Status Indicator
Fault Status
Indicator
Forward
Direction
Status Indicator
Reverse Direction
Status Indicator
External Reference
Indicator
External Sequence
Indicator
Fref Ref
12-16=005.00Hz
Monitor
12-17=000.00Hz
12-18=0000.0A
Fref Ref
12-16=005.00Hz
Monitor
12-17=000.00Hz
12-18=0000.0A