362 Adjust Menu (1 of 4)
Actual
Setting
The operating Mode for the control. MODE 1 is
for Heating. MODE 2 is for Snow Melting.
—1— (Heating)
—2— (Snow Melting)
Default = —1—
This item is the desired slab surface temperature
while in the Melting Mode.
MODE = —2—
32 to 95°F
(0 to 35°C)
Default = 36°F (2°C)
This item is the desired slab surface temperature
while in the Idling Mode.
MODE = —2—
OFF,
20 to 95°F or 120°F
(OFF, -7 to 35°C)
Default = OFF
The time for which the slab is operated once it
has reached the MELTING temperature. With-
MODE = —2—
OFF, 0:30 to 17:00 hr
INF (Infinity)
Default = 4:00 hr
The Cold Weather Cut Off temperature for the
snow melting system.
MODE = —2—
OFF, -30 to 50°F
(OFF, -34 to 10°C)
Default = 10°F (-12°C)
Occ
35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)
The desired room air temperature during an
Occupied period.
Note:
There is only a ±F
adjustment in the LTD access level.
DIP switch =
Characterized Heating Curve
RTU = NONE MODE = —1—
Section
LTD
INST
ADV
Range
Access
Level
DescriptionItem Field
USER
UnOcc
35 to 100°F
(2 to 38°C)
Default = 65°F (18°C)
The desired room air temperature during an
UnOccupied period.
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
RTU = NONE MODE = —1—
The device that is to be connected to the 10K
input terminal.
DIP switch =
Characterized Heating Curve
RTU = NONE MODE = —1—
NONE, INDR, ZoIn,
SLAB (only if MIX
MIN = Off)
Default = NONE
NONE, SLAB
Default = SLAB
Selects if a slab sensor is connected to the control.
MODE = —2—
OFF, 35 to 120°F
(OFF, 2 to 49°C)
Default = 70°F (21°C)
The minimum temperature at the slab sensor as
long as the control is not in WWSD.
DIP switch =
Characterized Heating Curve
10K = SLAB
MIX MIN = OFF
RTU = NONE MODE = —1—
The maximum temperature at the slab sensor.
DIP switch =
Characterized Heating Curve
10K = SLAB
RTU = NONE MODE = —1—
40 to 150°F
(4 to 66°C)
Default = 90°F (32°C)
A
C3
C4
C3
C4
C1
C1
B1
B1
B2
C3
C4
B2
B2
out slab sensor, countdown starts immediately.
This item cannot be viewed if a Remote Start /
Stop Module 039 has been connected.