Questions and Answers

  • A
    anthonynorrisSep 9, 2025
    Why is Telemark TVP-2000 Chiller system slow to cool?
    • C
      Cynthia MillerSep 10, 2025
      If the Telemark Chiller system is slow to cool, it could be because the cooling water temperature (WT) is lower than 15°C when the system is in standby. This can slow down the initial cooling process.
  • M
    michelle02Sep 12, 2025
    Why Telemark TVP-2000 enters defrost and terminates to standby?
    • T
      Tonya ThomasSep 12, 2025
      If the Telemark Chiller system momentarily enters defrost and then terminates to standby, it's likely because defrost was requested from standby. The system will only defrost if the coil is cold. Check if the value of CO is lower than the defrost termination point defined in cal2309 (default is zero oC.)
  • C
    crystal84Sep 14, 2025
    Why Telemark TVP-2000 has poor cooling performance?
    • N
      nmitchellSep 14, 2025
      If the Telemark Chiller system has poor cooling with a small temperature differential between CI and CO values, it might indicate a process problem. The TVP is designed to have a maximum stabilized temperature differential between CI and CO values of 20°C.
  • J
    Jacqueline BrownSep 16, 2025
    How to fix Telemark TVP-2000 LCD when it does not illuminate?
    • P
      peterrogersSep 16, 2025
      If the LCD on the Telemark Chiller does not illuminate, it could be due to no system power, a missing phase (Blue on machine), or the EMO not being reset. Check the mains input and reset the EMO by twisting it 90 degrees clockwise.