EasyManua.ls Logo

Tempcool TC-120B3 - TROUBLE SHOOTING GUIDE; Unit Does Not Run; Condensate Pump Issues; Compressor and Fan Operation

Default Icon
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6|Page
shoulddeflect0.25incheswith3poundsof
pressure.Newbeltscanloosenduringthefirst
hoursofoperation,sorecheckthebeltsafter
thefirst10hoursofoperationandthencheck
annually.Beltsshouldbereplacediftheyare
crackedorglazed.Driveshouldbereplacedif
they
aregroovedorworn.
Blowerfanbladescanbecomedirtyespecially
whenoperatingdirtyenvironmentswithout
filter.Thedirtwillbuilduponthebacksideof
thebladesandshouldbecleanoffitstartsto
cakeon.Fanperformanceisreducediflarge
quantitiesofdirtareonthe
blades.
SheaveAdjustment:
The condenser fan on the TC-120B series of air
conditioners utilizes an adjustable sheaves on
the motor to drive the blowers. The sheave is
preset at the factory and should not be adjusted.
However the blower, motor and drives should
periodically be checked for tightness and align-
ment. Check the setscrews that connect the
sheaves and blower wheel to the shafts to make
sure they are secure. Make sure the setscrews
locking down the adjustable flange on the motor
sheave are secure.
TROUBLESHOOTINGGUIDE
Problem Cause Remedy
Unitdoesnotrun
PhaseLightoff.
PowerLightdoesnot
comeon
Nopower Checkpowersupplyforcorrectvoltageandphase
CircuitbreakerOFF SwitchunitcircuitbreakerON
OFFONswitchOFF SwitchOFFONswitchtoON
Unitdoesnotrun.
PhaselightisON
Incomingpoweris out of
phasewiththeunit
Interchangeanytwolegsofthesupplypowerattheunit
circuitbreaker.Thelightshouldnotturnon.
Unitdoesnotrun.
PowerLightON
PhaseLightOFF
CondensateLightOFF
Thermostatnot
connected.
Plugthermostatplugintoreceptacleonsideofunit.
Thermostatnotsetto
COOLorsetpoint
temperatureabove
currenttemperature.
SetthermostattoCOOLandadjustthetemperature
settingbelowthecurrentthermostattemperature.The
airconditionershouldstart
Thermostatincorrectly
wiredordefective
Checkthermostat,cordandplugwiring.Replace
thermostatifdefective.
Unitdoesnotrun
CondensateLightON
Condensatepumpnot
working.
Checkwiringtocondensate pump.Repairorreplace
condensatepumpifrequired.
Callforcooling.
Evaporatorfanruns,
butcompressorand
condenserfandon’t
ControllerGreenlight
ON
Compressor2minute
timedelayedstartactive
Waitfortwominutestoseeifcompressorandfanstart
Thermostatinnotin
coolingmode
ChangethermostattoCOOL.Theremaystillbeatwo
minutedelayuntilthecompressorstarts.
ControllerLockout RefertoCopelandDigitalCompressorTroubleshooting
guideatthebackofthemanual.
HighorLowPressure
Switchestrippedor
defective.
Checksystempressureandchargewithgauges.Replace
switchesifrequired.
Compressorand
evaporatorcycleon
andoff
Cyclingoffofloworhigh
pressureswitch.
Checksystempressureandchargewithgauges.Replace
switchesifrequired.

Related product manuals