Backup Gateway 2 Specifications
Performance Specifications
AC Voltage (Nominal) 120/240 V
Feed-In Type Split Phase
Grid Frequency 60 Hz
Current Rating 200 A
Maximum Input Short Circuit Current
10 kA
1
Overcurrent Protection Device
100-200A; Service Entrance Rated
1
Overvoltage Category Category IV
AC Meter Revenue accurate (+/– 0.2 %)
1 
When protected by Class J fuses, Backup Gateway 2 is suitable for use in circuits capable of delivering not
mor
e than 22kA symmetrical amperes.
Mechanical Specifications
Dimensions 660 mm x 411 mm x 149 mm (26 in x 16 in x 6 in)
Weight 20.4 kg (45 lb)
Mounting Wall mount, Semi-flush mount
Environmental Specifications
Operating Temperature –20°C to 50°C (–4°F to 122°F)
Operating Humidity (RH) Up to 100%, condensing
Maximum Elevation 3000 m (9843 ft)
Environment Indoor and outdoor rated
Enclosure Type NEMA 3R