DC disconnect requirements between Powerwall and the inverter are subject to local codes.
Ensure that the installation meets local DC disconnect requirements. Check the inverter
installation manual to understand site connections and overcurrent protection.
All U.S. and Canada electrical installations must be done in accordance with local codes and the
National Electric Code (NEC) ANSI/NFPA 70 or the Canadian Electrical Code CSA C22.1.
All installations must conform to the laws, regulations, codes, and standards applicable in the
jurisdiction of installation.
MINIMUM SPACE REQUIREMENTS
Total ceiling height
Clear
ance above
Clearance below
2000 mm (6.5 ft )
300 mm (1 ft)
300 mm (1 ft)
Lateral wall space
Clearance from each side
1070 mm (42 in)
100 mm (4 in)
Depth of workspace
3
762 mm (30 in)
3
Depth r
equirement is typically determined by working clearances required in the local
installation code.
Site Requirements
Tesla