3.0 GENERAL INFORMATION
The Typhoon monitor is a 4-inch monitor. It is available in various manually operated models as well as an electric remote model.
The electric remote model is known as the Typhoon RC.
3.1 MECHANICAL SPECIFICATIONS
Manual Electric
US METRIC US METRIC
Weight 26 lbs 12 kg 38 lbs 17 kg
Min. Flow Area 4” Inlet 12.6 in
2
81.1 cm
2
12.6 in
2
81.1 cm
2
Min. Flow Area 3” Inlet 7.07 in
2
45.6 cm
2
7.07 in
2
45.6 cm
2
Max Operating Pressure 200 psi 14 bar 200 psi 14 bar
Materials Used ANSI A356.0-T6 Aluminum, Stainless, Nylon
Maximum Torque Elevation 70 ft•lbs 95 n•m
Maximum Torque Horizontal 60 ft•lbs 80 n•m
Speed Elevation 12 deg/sec
Speed Horizontal 12 deg/sec
Typhoon Operating Envelope
Flow (gpm)
Monitor Inlet Pressure (psi)
Flow (lpm)
Monitor Inlet Pressure (bar)
0
25
50
75
100
125
150
175
200
225
250
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
0
4
8
12
16
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Maximum Monitor
Inlet Pressure
Maximum Nozzle
Inlet Pressure
Monitor Loss
Nozzle D Inlet
Pressure
Nozzle C Inlet
Pressure
Nozzle B Inlet
Pressure
Nozzle A Inlet
Pressure
Nozzle A ows 500 gpm (1900 l/min), at 100 PSI (6.9 bar), K factor = 50
Nozzle B fl ows 1000 gpm (3800 l/min), at 100 PSI (6.9 bar), K factor = 100
Nozzle C fl ows 1500 gpm (5700 l/min), at 100 PSI (6.9 bar), K factor = 150
Nozzle D fl ows 2000 gpm (7600 l/min), at 100 PSI (6.9 bar), K factor = 200