G. Pump Selecon
AMPW
Model
Nominal
Pipe Size
(in)
Water
Hardness
(gpg)
Flow Rate
(GPM)
Heat Ex. loss
(ft of head)
Total Loss
(ft of head)
Optional
Grundfos*
Pump (TS #)
Temperature
Rise (F)
1000
3 4-12 99 11 17 109695-02 20
4 12-15 132 18 21 109695-04 15
1250
3 4-12 99 11 17 109695-02 24
4 12-15 132 18 21 109695-04 18
1500
3 4-12 110 10 17 109695-02 26
4 12-15 147 16 20 109695-04 20
2000
3 4-12 138 12 23 109695-04 28
4 12-15 183 18 23 109695-05 21
2500
4 4-12 214 13 20 109695-05 23
6 12-15 285 21 23 110025-01 17
3000
4 4-12 214 13 20 109695-05 27
6 12-15 285 21 23 110025-01 20
3500
4 4-12 280 11 24 110025-01 24
6 12-15 372 18 22 110025-01 18
4000
4 4-12 280 11 24 110025-01 28
6 12-15 372 18 22 110025-01 21
NOTE: The total loss includes 50 ft of pipe, 8 elbows, and 4 Valves.