APEX Installation, Operating, & Service Instructions
Altitude Model Fuel Recommended CO
2
Range
Percentage Derate
(approx. per 1,000 ft.)
2,001 ft.
to 4,500 ft.
APX425C
NG 8.6-9.2
2.3%
LP 9.4-10.2
APX525C
NG 8.7-9.2
4.1%
LP 9.8-10.1
APX625C
NG 8.6-9.2
0.0%
LP 9.4-9.9
APX725C
NG 8.2-8.7
1.7%
LP 9.2-9.7
APX825C
NG 8.2-9.1 1.2%
LP 9.4-10.0 0.0%
4,001 ft.
to 6,000 ft.
APX425C
NG 8.6-9.2
2.3%
LP 9.4-10.2
APX525C
NG 8.7-9.2
4.1%
LP 9.8-10.1
APX625C
NG 8.6-9.2
0.0%
LP 9.4-9.9
APX725C
NG 8.2-8.7
0.0%
LP 9.2-9.7
APX825C
NG 8.2-9.1 1.2%
LP 9.4-10.0 0.0%
6,001 ft.
to 7,800 ft.
APX425C
NG 8.6-9.2
2.2%
LP 9.4-10.0
APX525C
NG 8.7-9.2 3.6%
LP No Application No Application
APX625C
NG 8.6-9.2 0.7%
LP 9.4-9.7 1.2%
APX725C
NG 8.2-8.7
0.8%
LP 9.2-9.5
APX825C
NG No Application No Application
LP 9.4-9.8 1.4%
7,801 ft.
to 10,100 ft.
APX425C
NG 8.6-9.2
2.2%
LP 9.4-9.8
APX525C
NG 8.7-9.2 3.4%
LP No Application No Application
APX625C
NG 8.6-9.2
2.0%
LP 9.4-9.8
APX725C
NG 8.2-8.7 2.0%
LP No Application No Application
APX825C
NG No Application No Application
LP 9.4-9.7 2.8%
NOTE: De-rate’s per 1,000 ft. are approximate
**Based on minimum vent length**
Table A-4: Apex Altitude Adjustments
Appendix A Instructions for High Altitude Installations Above 2,000 ft.
(continued)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thermal Solutions APEX APX425C and is the answer not in the manual?

Thermal Solutions APEX APX425C Specifications

General IconGeneral
BrandThermal Solutions
ModelAPEX APX425C
CategoryBoiler
LanguageEnglish

Related product manuals