CSR-20 & CSR-40, September 1999
µP-D Controller Alarm Codes, Descriptions and Corrective Actions 4-53
Code Description Corrective Action
46 USDA 1 Sensor Failure (Option) • Check the sensor by selecting it using the View
(Check Alarm) menu. If USDA1 display shows [- - - -], the sensor
is defective or the circuit is open or shorted.
• Indicates a problem exists with this sensor
or its wiring. The sensor is reading out-of- • Check the sensor by substitution. Be sure the
range; or appears to be open or shorted. sensor polarity is correct.
• This sensor REQUIRES ice bath calibration. • Continuity check circuit wiring using a high quality
multimeter. Be sure to maintain the correct polarity
or the sensor will not work.
NOTE: Do NOT use a test light or other instru-
ment; or controller damage may result.
47 USDA 2 Sensor Failure (Option) • Check the sensor by selecting it using the View
(Check Alarm) menu. If USDA2 display shows [- - - -], the sensor
is defective or the circuit is open or shorted.
• Indicates a problem exists with this sensor
or its wiring. The sensor is reading out-of- • Check the sensor by substitution. Be sure the
range; or appears to be open or shorted. sensor polarity is correct.
• This sensor REQUIRES ice bath calibration. • Continuity check circuit wiring using a high quality
multimeter. Be sure to maintain the correct polarity
or the sensor will not work.
NOTE: Do NOT use a test light or other instru-
ment; or controller damage may result.
48 USDA 3 Sensor Failure (Option) • Check the sensor by selecting it using the View
(Check Alarm) menu. If USDA3 display shows [- - - -], the sensor
is defective or the circuit is open or shorted.
• Indicates a problem exists with this sensor
or its wiring. The sensor is reading out-of- • Check the sensor by substitution. Be sure the
range; or appears to be open or shorted. sensor polarity is correct.
• This sensor REQUIRES ice bath calibration. • Continuity check circuit wiring using a high quality
multimeter. Be sure to maintain the correct polarity
or the sensor will not work.
NOTE: Do NOT use a test light or other instru-
ment; or controller damage may result.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thermo King CSR-20 Series and is the answer not in the manual?

Thermo King CSR-20 Series Specifications

General IconGeneral
BrandThermo King
ModelCSR-20 Series
CategoryHeat Pump
LanguageEnglish

Related product manuals