TECHNICAL DATA
43
Residual current pickup value 0.002...2.00 I
En
0.002...0.999 I
En
(step 0.001 I
En
)
1.00...2.00 I
En
(step 0.01 I
En
)
Residual voltage pickup value 0.004...0.500 U
En
(step 0.001 U
En
)
Characteristic angle 0...359°
(step 1°)
Half operating sector 1...180°
(step 1°)
I
ED
>
inv
within CLP (I
EDCLP>>inv
) 0.002...2.00 I
En
0.002...0.999 I
En
(step 0.001 I
En
)
1.00...2.00 I
En
(step 0.01 I
En
)
Operating time (t
ED
>>
inv
) 0.02...60.0 s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
I
ED
>>> Element
CLP operating mode (I
EDCLP
>>>
Mode) OFF/ON-Element blocking/ON-Change setting
CLP activation time (t
EDCLP>>>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (t
ED
>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Third threshold definite time (I
ED
>>>
def
- U
ED
>>>
def
)
Residual current pickup value 0.002...10.00 I
En
0.002...0.999 I
En
(step 0.001 I
En
)
1.00...10.00 I
En
(step 0.01 I
En
)
Residual voltage pickup value 0.004...0.500 U
En
(step 0.001 U
En
)
Characteristic angle 0...359°
(step 1°)
Half operating sector 1...180°
(step 1°)
I
ED
>>>
def
within CLP (I
EDCLP
>>>
def
) 0.002...10.00 I
En
0.002...0.999 I
En
(step 0.001 I
En
)
1.00...10.00 I
En
(step 0.01 I
En
)
Operating time (t
ED
>>>
def
) 0.05...10.00 s (step 0.01 s)
I
ED
>>>> Element
CLP operating mode (I
EDCLP
>>>>
Mode) OFF/ON-Element blocking/ON-Change setting
CLP activation time (t
EDCLP>>>>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (t
ED
>>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Fourth threshold definite time (I
ED
>>>>
def
- U
ED
>>>>
def
)
Residual current pickup value 0.002...10.00 I
En
0.002...0.999 I
En
(step 0.001 I
En
)
1.00...10.00 I
En
(step 0.01 I
En
)
Residual voltage pickup value 0.004...0.500 U
En
(step 0.001 U
En
)
Characteristic angle 0...359°
(step 1°)
Half operating sector 1...180°
(step 1°)
I
ED
>>>>
def
within CLP (I
EDCLP
>>>>
def
) 0.002...10.00 I
En
0.002...0.999 I
En
(step 0.001 I
En
)
1.00...10.00 I
En
(step 0.01 I
En
)
Operating time (t
ED
>>>>
def
) 0.05...10.00 s (step 0.01 s)
I
ED
>>>>> Element
CLP operating mode (I
EDCLP
>>>>>
Mode) OFF/ON-Element blocking/ON-Change setting
CLP activation time (t
EDCLP>>>>>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (t
ED
>>>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Fifth threshold definite time (I
ED
>>>>>
def
- U
ED
>>>>>
def
)
Residual current pickup value 0.002...10.00 I
En
0.002...0.999 I
En
(step 0.001 I
En
)
1.00...10.00 I
En
(step 0.01 I
En
)
Residual voltage pickup value 0.004...0.500 U
En
(step 0.001 U
En
)
Characteristic angle 0...359°
(step 1°)
Half operating sector 1...180°
(step 1°)
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021

Table of Contents

Related product manuals