What to do if air vent ring is broken in TLV Control Unit?
- AAshley MillerSep 12, 2025
If the air vent ring (bimetal) in your TLV Control Unit is broken or worn, causing air-binding, replace the air vent ring.
What to do if air vent ring is broken in TLV Control Unit?
If the air vent ring (bimetal) in your TLV Control Unit is broken or worn, causing air-binding, replace the air vent ring.
Why is steam leaking from my TLV Plumbing Product outlet?
Steam leakage from the outlet of your TLV Plumbing Product can occur due to several reasons. It might be caused by rust or scale on the disc or module valve seat, which requires cleaning. Alternatively, the disc or module valve seat may be damaged or worn, necessitating replacement. Improper installation or product vibration could also be culprits; correct the installation or lengthen and secure the inlet piping. Finally, check if the operating pressure is below the minimum specified or if the back pressure exceeds allowable limits; compare specifications and actual operating conditions.
How to fix steam leaks from my TLV P Series Plumbing Product (not the outlet)?
If steam is leaking from somewhere other than the outlet on your TLV Plumbing Product, it could be due to gasket deterioration or damage, in which case you should replace the gaskets. Another possibility is that improper tightening torques were used, so you should tighten the components to the proper torque.
Why is my TLV Control Unit steam leaking or blowing from the valve seat?
Steam leakage or blowing from the valve seat in your TLV Control Unit can occur if the valve closure is obstructed by scale or other debris. To resolve this, clean or replace the screen.
What to do if steam-locking has occurred in TLV Control Unit?
If steam-locking has occurred in your TLV Control Unit, perform a bypass blow-down, or close the trap inlet valve and allow the trap to cool. Piping correction may also be required.
What to do if no condensate is discharged from my TLV Plumbing Product?
If your TLV Plumbing Product isn't discharging condensate properly, it could be due to several issues: * The module valve seat, screen, or piping might be clogged with rust or scale. If this is the case, clean the parts. * The disc may be stuck to the module valve seat. If this is the case, clean the parts. * Air binding may have occurred. Try a bypass blowdown, or close the trap inlet valve and allow the trap to cool. * Air binding could also be due to disc holder ring or air vent ring wear. Replace these with new ones. * Steam-locking might be the cause. Perform a bypass blowdown, or close the trap inlet valve and allow the trap to cool. Piping correction may also be required. * The operating pressure might be below the minimum specified pressure, or there might be insuffici...
How to fix a worn disc or valve seat in TLV Control Unit?
If the disc or valve seat is worn in your TLV Control Unit, replace the disc or valve seat.
What to do if screen holder is loose in TLV Control Unit?
If the screen holder is loose or the screen holder gasket is damaged in your TLV Control Unit, tighten the screen holder or replace the screen holder gasket.
What to do if the screen is clogged with rust or scale in TLV Control Unit?
If the screen in your TLV Control Unit is clogged with rust or scale, clean it.
How to fix a loose cover on TLV Control Unit?
If the cover of your TLV Control Unit is loose or the module gaskets are damaged, tighten the cover or replace the module gaskets.