Instruction Manual
Thermodynamic Steam Trap: P Series
Featured Models: P46SRN/P46SRM//P46SRW/P65SRN
172-65530MJ-07
Publication date 28 August 2023
Copyright © 2023 TLV CO., LTD.

Questions and Answers

  • J
    jamespayneSep 10, 2025
    What to do if air vent ring is broken in TLV Control Unit?
    • A
      Ashley MillerSep 12, 2025
      If the air vent ring (bimetal) in your TLV Control Unit is broken or worn, causing air-binding, replace the air vent ring.
  • P
    prichardsAug 25, 2025
    Why is steam leaking from my TLV Plumbing Product outlet?
    • K
      Karina HarrisAug 26, 2025
      Steam leakage from the outlet of your TLV Plumbing Product can occur due to several reasons. It might be caused by rust or scale on the disc or module valve seat, which requires cleaning. Alternatively, the disc or module valve seat may be damaged or worn, necessitating replacement. Improper installation or product vibration could also be culprits; correct the installation or lengthen and secure the inlet piping. Finally, check if the operating pressure is below the minimum specified or if the back pressure exceeds allowable limits; compare specifications and actual operating conditions.
  • E
    Edward HartAug 27, 2025
    How to fix steam leaks from my TLV P Series Plumbing Product (not the outlet)?
    • J
      Jennifer EllisAug 27, 2025
      If steam is leaking from somewhere other than the outlet on your TLV Plumbing Product, it could be due to gasket deterioration or damage, in which case you should replace the gaskets. Another possibility is that improper tightening torques were used, so you should tighten the components to the proper torque.
  • C
    Colleen WellsAug 27, 2025
    Why is my TLV Control Unit steam leaking or blowing from the valve seat?
    • B
      Brittany SimpsonAug 27, 2025
      Steam leakage or blowing from the valve seat in your TLV Control Unit can occur if the valve closure is obstructed by scale or other debris. To resolve this, clean or replace the screen.
  • S
    Stephanie MartinezAug 29, 2025
    What to do if steam-locking has occurred in TLV Control Unit?
    • T
      Tracy MitchellAug 29, 2025
      If steam-locking has occurred in your TLV Control Unit, perform a bypass blow-down, or close the trap inlet valve and allow the trap to cool. Piping correction may also be required.
  • E
    Elizabeth HartmanNov 21, 2025
    What to do if no condensate is discharged from my TLV Plumbing Product?
    • J
      Johnny RyanNov 21, 2025
      If your TLV Plumbing Product isn't discharging condensate properly, it could be due to several issues: * The module valve seat, screen, or piping might be clogged with rust or scale. If this is the case, clean the parts. * The disc may be stuck to the module valve seat. If this is the case, clean the parts. * Air binding may have occurred. Try a bypass blowdown, or close the trap inlet valve and allow the trap to cool. * Air binding could also be due to disc holder ring or air vent ring wear. Replace these with new ones. * Steam-locking might be the cause. Perform a bypass blowdown, or close the trap inlet valve and allow the trap to cool. Piping correction may also be required. * The operating pressure might be below the minimum specified pressure, or there might be insuffici...
  • L
    Louis VelasquezSep 18, 2025
    How to fix a worn disc or valve seat in TLV Control Unit?
    • V
      Victor CameronSep 18, 2025
      If the disc or valve seat is worn in your TLV Control Unit, replace the disc or valve seat.
  • J
    Juan MackSep 23, 2025
    What to do if screen holder is loose in TLV Control Unit?
    • M
      Michelle CowanSep 23, 2025
      If the screen holder is loose or the screen holder gasket is damaged in your TLV Control Unit, tighten the screen holder or replace the screen holder gasket.
  • C
    Cheryl HigginsSep 9, 2025
    What to do if the screen is clogged with rust or scale in TLV Control Unit?
    • C
      Cristina BurnettSep 9, 2025
      If the screen in your TLV Control Unit is clogged with rust or scale, clean it.
  • T
    Tamara WilsonSep 5, 2025
    How to fix a loose cover on TLV Control Unit?
    • J
      Jason CantrellSep 6, 2025
      If the cover of your TLV Control Unit is loose or the module gaskets are damaged, tighten the cover or replace the module gaskets.