TOPVERT G1/H1/P1 Series
E-31
Group 8: Fan & Pump Control Parameters
Paramet
ers
Functions Settings
Factory
Setting
User
Pr8-00 V/F Curve Selection
0: V/F Curve determined by Parameter Group 1
0
1: 1.5 Power Curve
2: Square Power Curve
Pr8-01
Start-Up Frequency of the
Auxiliary Motor
0.00
600.00 Hz (H1:00.0
6000.0Hz)
0.00
Pr8-02
Stop Frequency of the Auxiliary
Motor
5.00
600.00 Hz (H1:50.0
6000.0Hz)
5.00
Pr8-03
Time Delay before Stopping the
Auxiliary Motor
0.0
6000.0 Sec 0.00
Pr8-04
Time Delay before Stopping the
Auxiliary Motor
0.0
6000.0 Sec 0.00
Pr8-05 Sleep Frequency
0.00
600.00 Hz (H1:00.0
6000.0Hz)
0.00
Pr8-06 Wake-up Frequency
0.00
600.00 Hz (H1:00.0
6000.0Hz)
0.00
Pr8-07 Sleep Time 0.0
6000.0 Sec 0.0
Group 9: Speed Feedback Control Parameters
(A PG Feedback Card (optional) is necessary for setting those parameters)
Parameters
Functions Settings
Factory
Setting
User
Pr9-00
PG Pulses
1~5000 PPR 1024
Pr9-01
PG Type and Function setting
0 : Disable PG
0
1: Bidirection, Phase A leads in a forward
run command and phase B leads in a
reverse run command
2: Bidirection, Phase B leads in a forward
run command and phase A leads in a
reverse run command
4: As PID feedback (REV)
5: As PID feedback (FWD)
8: Frequency command (REV) ( Pr0-18=4 )
9: Frequency command (FWD) ( Pr0-18=4 )
Pr9-02
PG Speed Feedback Display
Filter
0.000~1.000sec 0.03
Pr9-03
PG feedback speed control
Proportional Gain (P)
0.0
500.0% 20.0
Pr9-04
PG feedback speed control
Integral Time (I)
0.00
10.00 Sec
0.50
0.00 : no integral
Pr9-05
PG feedback speed control
Differential (D) Time
0.00
5.00 Sec
0.00
Pr9-06
PG Speed Control Output
Frequency Limit
0.00~150.00Hz
20.00
Pr9-07 Treatment of PG Feedback Fault
0: warn and keep operating
0
1: warn and RAMP to stop
2: warn and COAST to stop
Pr9-08
PG Feedback Fault Detection
Time
0.00~10.00 Sec 0.10
Pr9-09 PG Feedback compensation limit 0~900 RPM 90