TOPVERT G1/H1/P1 Series
E-30
Pr6-15
Dwell Frequency at Accel. 0.00
~
600.00 Hz (H1:00.0
~
6000.0Hz) 6.00
Pr6-16
Dwell Time at Decel. 0.00~60.00 Sec 0.00
Pr6-17
Dwell Frequency at Decel. 0.00
~
600.00 Hz (H1:00.0
~
6000.0Hz) 6.00
Pr6-18
Dwell Frequency current Amp (0~150% of rated current) ##.##
Pr6-19
Traverse Skip Frequency 0.00~100.00Hz 0.00
Pr6-20
The Amplitude of traverse 0.00~200.00Hz 0.00
Group 7: High-function Parameters (PID and Communication)
Parame
ters
Functions Settings
Factory
Setting
User
Pr7-00
Proportional Gain (P) 0.0
~
500.0% 80.0
Pr7-01
Integral Time (I)
0.00
~
100.00 Sec
1.00
0.00
:
no integral
Pr7-02
Derivative Control (D) 0.00
~
5.00 Sec 0.00
Pr7-03
Upper limit for Integral Control 0.0
~
100.0% 100.0
Pr7-04
PID Output Frequency Limit 0.0
~
100.0% 100.0
Pr7-05
PID Offset -100.0~+100.0% 0.0
Pr7-06
Primary Delay Filter Time 0.000~0.100 Sec 0.000
Pr7-07
PID Feedback Signal Detection Time 0.0
~
6000.0 Sec 0.0
Pr7-08
Treatment of the Erroneous PID
Feedback Signals
0: warn and keep operating
0
1: warn and RAMP to stop
2: warn and COAST to stop
Pr7-9
Treatment of Keypad Transmission
Fault
0: Warn and RAMP to stop
0
1: Warn and COAST to stop
Pr7-10
Keypad Transmission Fault detection
0.0: Disable and keep operating
0.0
0.1~60.0 Sec
Pr7-11
Communication Address
1
~
254 1
Pr7-12
Transmission Speed (Baud rate)
1.2
~
125 Kbps 9.6
Pr7-13
Transmission Fault Treatment
0: warn and keep operating
3
1: warn and RAMP to stop
2: warn and COAST to stop
3: No warning and keep operating
Pr7-14
Time-out Detection
0.0: disabled
0.0
0.1~60.0 Sec
Pr7-15
Communication Protocol
0
:
7,N,2 ASCII
0
1
:
7,E,1 ASCII
2
:
7,O,1 ASCII
3
:
7,E,2 ASCII
4
:
7,O,2 ASCII
5
:
8,N,1 ASCII
6
:
8, N,2 ASCII
7
:
8,E,1 ASCII
8
:
8,O,1 ASCII
9
:
8,E,2 ASCII
10
:
8,O,2 ASCII
11
:
8,N,1 RTU
12
:
8,N,2 RTU
13
:
8,E,1 RTU
14
:
8,O,1 RTU
15
:
8,E,2 RTU
16
:
8,O,2 RTU