TOPVERT G1/H1/P1 Series
E-29
◎
Pr5-46
Motor 2- Electronic Thermal Relay
Characteristic
30
~
600 Sec
60
◎
Pr5-47
Heatsink Over-Heat pre–warning
setting (oH2)
0.0
~
110.0
℃
85.0
◎
Pr5-48 Delay Time for Motor Selection
0.00~60.00 Sec
0.05
◎
Pr5-49 Motor selection mode
Bit 0
(bxxxx0)
0
Cannot be switch during
operation.
b00000
1
Can be switch during
operation.
Bit 1
(bxxxx0)
0
No need to waiting for
confirm signal when
switching
1
Need to waiting for
confirm signal when
switching
Group 6: Special Parameters
Parame
ters
Functions Settings
Factory
Setting
User
Pr6-00
DC Braking Current Level Amp (0~125% of drive’s rated current) ##.##
Pr6-01
DC Braking Time during
Start-up
0.00
~
60.00 Sec 0.00
Pr6-02
DC Braking Time during
stopping
0.00
~
60.00 Sec 0.00
Pr6-03
Start-point for DC Braking
during stopping
0.00
~
600.00 Hz (H1:00.0
~
6000.0Hz) 0.00
Pr6-04
Increasing Rate of the DC
Braking Voltage
0.01~300.00% 20.00
Pr6-05
Momentary Power Loss
Operation Selection
0
:
Operation stops after momentary power loss.
0
1
:
Operation continues after momentary power loss,
speed search Speed Search starts with Last
Output Frequency Downward
2
:
Operation continues after momentary po
speed search starts with the Start-up frequency
Upward
Pr6-06
Maximum Allowable Power
Loss Time
0.1
~
5.0 Sec 2.0
Pr6-07
Base-Block Time for Speed
Search (BB)
0.1
~
5.0 Sec 0.5
Pr6-08
Maximum Current Level for
Speed Search
Amp(20
~
200% of drive’s rated current) ##.##
Pr6-09
Deceleration Time for Speed
Search
0.50
~
120.00 Sec 3.00
Pr6-10
Auto Restart after Fault 0
~
30 times 0
Pr6-11
Speed Search during Start-up
0
:
speed search disabled
0
1
:
speed search through the frequency command
2
:
FWD-speed search only
(motor only runs in FWD direction)
3
:
REV-speed search only
(motor only runs in REV direction)
4
:
FWD/REV speed search enabled in both directions
(FWD first)
5
:
REV/FWD speed search enabled in both directions
(REV first)
Pr6-12
Speed Search Frequency
(FWD direction)
0.00
~
600.00 Hz (H1:00.0
~
6000.0Hz)
60.00/
50.00
Pr6-13
Speed Search Frequency
(REV direction)
0.00
~
600.00 Hz (H1:00.0
~
6000.0Hz)
60.00/
50.00
Pr6-14
Dwell Time at Accel. 0.00~60.00 Sec 0.00