TOPVERT L1 Series
E-
16
Pr0-22
Waiting time to restart
after stop
0.00~60.00sec
0.00
Pr0-23
Cooling fan control & PID
direction
Bit 0
(bxxxx0)
0: Fan on while power on
b00000
1: Fan on while run command effect
Bit 1
(bxxx0x)
(Factory Reserved)
Bit 2
(bxx0xx)
(Factory Reserved)
Bit 3
(bx0xxx)
0: PID reverse operation allow
1: PID reverse operation not allow
Bit 4
(b0xxxx)
(Factory Reserved)
Pr0-24
Resolution of dial
0=0.01 Hz
1
1=0.10Hz
2=1.00Hz
3=10.00 Hz
★
◎
Pr0-25
Parameter select
0: Team A
0
1: Team B
2: (Factory Reserved)
Group 1: Basic parameters
Paramet
ers
Functions Settings
Factory
Setting
User
★
Pr1-00
Maximum operation frequency
3.00~600.00Hz 60.00/50.00
★
Pr1-01
1st Frequency 1 (Fbase 1)
(Base frequency 1 )
0.00~600.00 Hz 60.00/50.00
Pr1-02
1st Voltage 1 (Vbase 1)
(Motor rated voltage 1)
230V models:
0.0~255.0V
460V models:
0.0~510.0V
230V:230.0
460V:460.0
★
Pr1-03
2nd Frequency 1 (Fmid 1)
(Middle frequency 1)
0.00~600.00 Hz
0.50
Pr1-04
2nd Voltage 1 (Vmid 1)
(Middle voltage 1)
230V models:
0.0~255.0V
460V models:
0.0~510.0V
230V:5.0
460V:10.0
★
Pr1-05
3rd Frequency 1 (Flow 1)
(Low-point frequency 1)
0.00~600.00 Hz 0.50
Pr1-06
3rd Voltage 1 (Vlow 1)
(Low-point voltage 1)
230V models:
0.0~255.0
460V models:
0.0~510.0V
230V:5.0
460V:10.0
Pr1-07
0Hz Voltage 1 (V0Hz 1)
(Output voltage at 0Hz)
230V models:
0.0~25.5
460V models:
0.0~51.0V
0.0
Pr1-08
Start-up frequency
0.00~600.00 Hz
0.50
Pr1-09 Output frequency Upper limit
0.0~150.0% of Maximum operation
frequency (Pr1-00)
110.0
Pr1-10
Output Frequency Lowerl limit
0.0~100.0% of Maximum operation
frequency (Pr1-00)
0.0
Pr1-11
1
Acceleration time
0.00~60000 Sec 10.00/60.00
Pr1-12
1
Deceleration time
0.00~60000 Sec 10.00/60.00
Pr1-13
2
nd
Acceleration time
0.00~60000 Sec 10.00/60.00
Pr1-14
2
nd
Deceleration time
0.00~60000 Sec 10.00/60.00
Pr1-15
(Factory Reserved) (Factory Reserved)
Pr1-16
(Factory Reserved)
(Factory Reserved)
Pr1-17
(Factory Reserved)
(Factory Reserved)