Preventive Maintenance
Toshiba's 1600 Series of uninterruptible power systems have been designed to provide years of
trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the unit,
particularly the air inlet vents, clean and free of moisture and dust accumulations.
If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically
remove dust accumulations around and from the unit.
Only a qualified Toshiba Representative should be
allowed to perform any routine maintenance or service
on this equipment other than those preventive maintenance
details which are described directly above this caution.
Parts Replacement
The following list shows recommended intervals for periodic replacement of certain UPS parts:
1) Batteries: In order to maintain system reliability, the UPS unit's batteries
should be replaced on a regular schedule. To ensure reliable operation, all
of the batteries should be replaced at the same time. Use the following
chart for replacement:
2) Aluminum electrolytic capacitors: Replace once every 5 years.
3) Fuses: Replace once every 7 years.
4) Cooling fan: When operated in an ambient temperature of 30° C (86° F) to 40° C (104° F),
replace every 3.5 years.
When operated in an ambient temperature of less than 30° C (86° F) ,
replace every 5 years.
CAUTION
42
UPS Battery Replacement
TOSHIBA
Preventive Maintenance/Parts Replacement
Battery lifetime Batt Amb Temp Average lifetime (% Reduced)
(When discharged once 20-25° C (68-77° F) Approx. 5 yrs 0%
every 3 months to 100% 30° C (86° F) Approx. 3.5 yrs 30%
depth of discharge; data 35° C (95° F) Approx. 2.5 yrs 50%
published by Yuasa 40° C (104° F) Approx. 1.8 yrs 66%
battery manufacturer) 45° C (113° F) Approx. 1.25 yrs 75%