EasyManua.ls Logo

Toshiba CARRIER RAV-SP180AT2-UL - Capacity Variation Ratio According to Temperature

Toshiba CARRIER RAV-SP180AT2-UL
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 11 –
RAV-SP300AT2-UL, RAV-SP360AT2-UL, RAV-SP420AT2-UL
<Cooling> <Heating>
020406080
Compressor speed (rps)
0
22
20
18
16
14
12
8
10
6
4
2
0
22
20
18
16
14
12
8
10
6
4
2
Current (A)
Current (A)
020406080
Compressor speed (rps)
• Conditions
Indoor : DB 80.6˚F (27˚C)/
WB 66.2˚F (19˚C)
Outdoor : DB 95˚F (35˚C)
Air flow : High
Pipe length : 295.3” (7.5m)
230V
• Conditions
Indoor : DB 68˚F (20˚C)
Outdoor : DB 44.6˚F (7˚C)/
WB 42.8˚F (6˚C)
Air flow : High
Pipe length : 295.3” (7.5m)
230V
RAV-SP300AT2-UL
RAV-SP300AT2-UL
RAV-SP360AT2-UL,
RAV-SP360AT2-UL,
RAV-SP420AT2-UL
RAV-SP420AT2-UL
RAV-SP300AT2-UL
RAV-SP300AT2-UL
RAV-SP360AT2-UL,
RAV-SP360AT2-UL,
RAV-SP420AT2-UL
RAV-SP420AT2-UL
RAV-SP300AT2-UL
RAV-SP360AT2-UL,
RAV-SP420AT2-UL
RAV-SP300AT2-UL
RAV-SP360AT2-UL,
RAV-SP420AT2-UL
Capacity variation ratio according to temperature
RAV-SP180AT2-UL, RAV-SP240AT2-UL, RAV-SP300AT2-UL, RAV-SP360AT2-UL, RAV-SP420AT2-UL
<Cooling> <Heating>
50
55
60
65
70
75
80
85
90
95
100
105
89.6
(32)
91.4
(33)
93.2
(34)
95
(35)
96.8
(36)
98.6
(37)
100.4
(38)
102.2
(39)
104
(40)
105.8
(41)
107.6
(42)
109.4
(43)
Outdoor temp. ˚F (˚C)
Capacity ratio (%)
0
10
20
30
40
50
60
70
80
90
100
110
120
6.8
(–14)
3.2
(–16)
–0.4
(–18)
–4
(–20)
10.4
(–12)
14
(–10)
17.6
(–8)
21.2
(–6)
24.8
(–4)
28.4
(–2)
32
(0)
35.6
(2)
39.2
(4)
42.8
(6)
46.4
(8)
50
(10)
Outdoor temp. ˚F (˚C)
Capacity ratio (%)
• Conditions
Indoor : DB 68˚F (20˚C)
Indoor air flow : High
Pipe length : 295.3” (7.5m)
• Conditions
Indoor : DB 80.6˚F (27˚C)/
WB 66.2˚F (19˚C)
Indoor air flow : High
Pipe length : 295.3” (7.5m)