EasyManua.ls Logo

Toshiba Carrier RAV-SP180KRT-UL - Page 17

Toshiba Carrier RAV-SP180KRT-UL
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
High-Wall Type
Installation Manual
–16–
Toshiba
EN
Open the valve fully
Open the valve of the outdoor unit fully. A 4 mm
hexagon wrench is required for opening the valve.
For details, refer to the Installation Manual attached
to the outdoor unit.
Gas leak check
Check with a leak detector or soap water whether
gas leaks or not, from the pipe connecting section
or cap of the valve.
REQUIREMENT
Use a leak detector manufactured exclusively for
HFC refrigerant (R410A, R134a, etc.).
Wireless remote control A-B
selection
Using 2 wireless remote controllers for the
respective air conditioners, when the 2 air
conditioners are closely installed.
Wireless remote controller B setup
1. Press button on the indoor unit to turn the air
conditioner ON.
2. Point the wireless remote controller at the indoor unit.
3. Push and hold button on the wireless remote
controller by the tip of the pencil.
“00” will be shown on the display.
4. Press during pushing . “B” will be shown on
the display and “00” will be disappear and the air
conditioner will turn OFF. The wireless remote
controller B is memorized.
NOTE
Repeat above step to reset wireless remote
controller to be A.
The wireless remote controllers do not display
“A”.
The factory default of the wireless remote
controllers is “A”.
CHK
MODE
CHK
PRESET FAN
"B" Display
"00" Display
16-EN
+001111052201_00Ta.book Page 16 Friday, November 20, 2009 11:45 AM

Related product manuals