R410A
FILE NO. A10-019-1
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
PRINTED IN JAPAN, Dec., 2011 ToMo
INDOOR UNIT
4-Way Cassette Type
MMU-AP0182H2UL, MMU-AP0212H2UL,
MMU-AP0242H2UL, MMU-AP0302H2UL,
MMU-AP0362H2UL, MMU-AP0422H2UL
Compact 4-Way Cassette Type
MMU-AP0071MH2UL, MMU-AP0091MH2UL,
MMU-AP0121MH2UL, MMU-AP0151MH2UL,
MMU-AP0181MH2UL
Ceiling Type
MMC-AP0181H2UL, MMC-AP0241H2UL,
MMC-AP0361H2UL, MMC-AP0421H2UL
High Wall Type
MMK-AP0073H2UL, MMK-AP0093H2UL,
MMK-AP0123H2UL, MMK-AP0153H2UL,
MMK-AP0183H2UL, MMK-AP0243H2UL
4-Way Cassette Type
Compact 4-Way Cassette Type
Ceiling Type
High Wall Type
REVISION 1 : Dec.2011
Re-edit version.( file volume down)
Contents have NOT been changed.

Other manuals for Toshiba Carrier MMU-AP0091MH2UL

Question and Answer IconNeed help?

Do you have a question about the Toshiba Carrier MMU-AP0091MH2UL and is the answer not in the manual?

Toshiba Carrier MMU-AP0091MH2UL Specifications

General IconGeneral
BrandToshiba
ModelCarrier MMU-AP0091MH2UL
CategoryAir Conditioner
LanguageEnglish

Summary

Safety Cautions and Warnings

Explanation of Indications and Marks

Explains warning symbols, text indicators, and illustrated safety marks.

Confirmation of Warning Label on Main Unit

Instructions to confirm and re-apply warning labels on the unit.

New Refrigerant R410A Safety and Handling

Safety Caution for New Refrigerant

Cautions for R410A refrigerant, its higher pressure, and oil changes.

Cautions on Installation and Service

Specific warnings for installation and service of R410A systems.

Pipe Materials Selection

Guidelines for selecting appropriate copper pipes and flare nuts for R410A.

Required Tools for R410A

Required Tools for R410A

Lists tools exclusive and interchangeable for R410A refrigerant.

General Tools for R410A

Lists common tools also necessary for R410A work.

1. SPECIFICATIONS

1-1. 4-Way Cassette Type Specifications

Technical specifications for 4-way cassette indoor units.

1-2. Compact 4-Way Cassette Type Specifications

Technical specifications for compact 4-way cassette indoor units.

1-3. Ceiling Type Specifications

Technical specifications for ceiling type indoor units.

1-4. High Wall Type Specifications

Technical specifications for high wall type indoor units.

2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)

2-1. 4-Way Cassette Type Views

External views and dimensions for 4-way cassette indoor units.

MMU-AP0212H2UL, MMU-AP0242H2UL, MMU-AP0302H2UL Views

External views and dimensions for specific 4-way cassette models.

MMU-AP0362H2UL, MMU-AP0422H2UL Views

External views and dimensions for specific 4-way cassette models.

2-2. Compact 4-Way Cassette Type Views

External views and dimensions for compact 4-way cassette indoor units.

MMU-AP0151MH2UL, MMU-AP0181MH2UL Views

External views and dimensions for specific compact 4-way cassette models.

2-3. Ceiling Type Views

External views and dimensions for ceiling type indoor units.

MMC-AP0241H2UL Views

External views and dimensions for a specific ceiling type model.

MMC-AP0361H2UL, MMC-AP0421H2UL Views

External views and dimensions for specific ceiling type models.

2-4. High Wall Type Views

External views and dimensions for high wall type indoor units.

MMK-AP0153H2UL, MMK-AP0183H2UL Views

External views and dimensions for specific high wall type models.

MMK-AP0243H2UL Views

External views and dimensions for a specific high wall type model.

3. WIRING DIAGRAM

3-1. 4-Way Cassette Type Wiring

Wiring diagrams for 4-way cassette indoor units.

3-2. Compact 4-Way Cassette Type Wiring

Wiring diagrams for compact 4-way cassette indoor units.

3-3. Ceiling Type Wiring

Wiring diagrams for ceiling type indoor units.

3-4. High Wall Type Wiring

Wiring diagrams for high wall type indoor units.

4. PARTS RATING

4-1. 4-Way Cassette Type Parts Rating

Parts ratings for 4-way cassette indoor units.

4-2. Compact 4-Way Cassette Type Parts Rating

Parts ratings for compact 4-way cassette indoor units.

4-3. Ceiling Type Parts Rating

Parts ratings for ceiling type indoor units.

4-4. High Wall Type Parts Rating

Parts ratings for high wall type indoor units.

5. REFRIGERATING CYCLE DIAGRAM

6. CONTROL OUTLINE

6-1. Cassette and Ceiling Type Control Outline

Control outlines for 4-way cassette, compact cassette, and ceiling type indoor units.

Automatic Capacity Control

Explanation of automatic capacity control based on temperature differences.

Air Speed Selection

How air speed is selected and controlled in cooling and heating modes.

Prevention of Cold Air Discharge

Measures to prevent cold air discharge during heating operation.

Freeze Prevention and Oil Recovery Controls

Control logic for freeze prevention and refrigerant oil recovery.

Intermittent Operation and Filter Display

Controls for intermittent operation, retained heat, and filter sign display.

Louver and Hi POWER Controls

Setup and operation of louvers and Hi POWER function.

Specialized Operations: COMFORT SLEEP, PRESET, QUIET, SLEEP, Save

Details on COMFORT SLEEP, PRESET, QUIET, SLEEP, and Save operations.

6-2. High Wall Type Control Outline

Power Reset and Operation Mode Selection

Behavior upon power reset and operation mode selection.

Temperature, Capacity, and Air Speed Control

Control logic for room temperature, capacity, and air speed.

Discharge Prevention and Freeze Control

Prevention of cold air discharge and freeze prevention control.

Oil Recovery and Other Controls

Controls for refrigerant oil recovery and intermittent operations.

Specialized Operations: Hi POWER, COMFORT SLEEP, PRESET

Details on Hi POWER, COMFORT SLEEP, and PRESET operations.

7. APPLIED CONTROL AND FUNCTION

7-1. Indoor Controller Block Diagrams

Block diagrams for indoor controllers with different remote configurations.

7-2. Indoor Printed Circuit Board

Illustrations and labeling of indoor P.C. boards for different unit types.

7-3. Functions at Test Run

Procedures for performing cooling/heating test runs and wireless controller tests.

Indoor Unit Operation Check

Checking indoor unit operation using P.C. board pins.

7-4. Method to Set Indoor Unit Function DN Code

Procedure for setting indoor unit function DN codes using the remote controller.

7-5. Applied Control in Indoor Unit

Details on remote location ON/OFF control, fan control, and prevention controls.

Address Setup from Wired Remote Controller

Procedure for manual address setup using a wired remote controller.

Function to Clear Error

Methods for clearing errors from the remote controller or indoor unit.

Monitoring Function of Remote Controller Switch

How to use the monitoring function of the remote controller.

Changing Settings for Celsius Display

Procedure to change settings from Celsius to Fahrenheit display.

8. TROUBLESHOOTING

8-1. Overview

Overview of troubleshooting, applicable models, tools, and general checks.

8-2. Troubleshooting Method

Method for troubleshooting based on check codes displayed on controllers and boards.

Check Codes (Indoor Unit Errors)

List of check codes for indoor unit errors and their typical faults.

Check Codes (Main Remote Controller)

List of check codes detected by the main remote controller.

Check Codes (Central Control Device)

List of check codes detected by the central control device.

Check Codes (Outdoor Unit Errors)

List of check codes for outdoor unit errors and their causes.

8-3. Troubleshooting Based on Remote Controller Display

Troubleshooting based on information displayed on the remote controller, including error history.

Indoor Unit Indicators (Wireless Type)

How to identify check codes using indoor unit indicators for wireless type.

Other Indications

Other indications that do not involve check codes, such as test run status.

8-4. Check Codes on Controllers and Outdoor Unit

Detailed list of check codes displayed on controllers and I/F boards with check items.

Errors Detected by TCC-LINK Central Control Device

List of errors detected by the TCC-LINK Central Control Device.

8-5. Sensor Characteristics

Graphs showing resistance vs. temperature for indoor sensors.

9. DETACHMENTS

9-1. 4-Way Cassette Type Detachments

Detachment and attachment procedures for parts of 4-way cassette units.

9-2. Compact 4-Way Cassette Type Detachments

Detachment and attachment procedures for parts of compact 4-way cassette units.

9-3. Ceiling Type Detachments

Detachment and attachment procedures for parts of ceiling type units.

9-4. High Wall Type Detachments

Detachment and attachment procedures for parts of high wall type units.

10. P.C. BOARD EXCHANGE PROCEDURES

10-1. Cassette and Ceiling Type P.C. Board Exchange

Procedures for exchanging P.C. boards for cassette and ceiling types.

Procedure 1: Reading Setting Data from EEPROM

Steps to read setting data from EEPROM using the remote controller.

Procedure 2: Replacing P.C. Board

Steps to replace the faulty P.C. board with a service P.C. board.

Procedure 3: Writing Setting Data in EEPROM

Steps to write setting data into the EEPROM of the service P.C. board.

CODE No. List Example

Example list of CODE No. (DN) items, setting data, and factory values.

10.2 High Wall Type P.C. Board Exchange

Replacement Procedure Overview

Overview of the P.C. board replacement procedure for High Wall type units.

Method 1: Reading Setup Data from EEPROM

Procedure to read setup data via remote controller before replacement.

Procedure 1: Readout of Setup Data from EEPROM

Steps to read setup data from EEPROM using the remote controller.

Procedure 2: Service P.C. Board Replacement

Steps to replace the P.C. board and establish correspondence.

Procedure 3: Writing Setting Data in EEPROM

Steps to write setting data into the EEPROM of the service P.C. board.

CODE No. Table for Unit Data

Table for recording objective unit data, including CODE No. and capacity.

11. EXPLODED VIEWS AND PARTS LIST

11-1. 4-Way Cassette Type Views

Exploded views and parts lists for 4-way cassette units.

MMU-AP0362H2UL, AP0422H2UL Exploded View

Exploded view for specific 4-way cassette models.

11-2. Compact 4-way Cassette Type Views

Exploded views and parts lists for compact 4-way cassette units.

11-3. Ceiling Type Views

Exploded views and parts lists for ceiling type units.

11-4. High Wall Type Views

Exploded views and parts lists for high wall type units.

WARNINGS ON REFRIGERANT LEAKAGE

Check of Concentration Limit

Requirements for refrigerant concentration limits in rooms.