3
Secure the outdoor unit with xing bolts and nuts if the unit is likely to be
exposed to a strong wind.
Use Ø8 mm or Ø10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach drain nipple 7 and cap
water proof 8 to the bottom plate of the outdoor unit before installing it.
Fixing bolt arrangement of outdoor unit
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
Part
code
Parts name Q’ty
A
Refrigerant piping
Liquid side : Ø6.35 mm
Gas side : Ø9.52 mm
(RAS-10, 13G2KVP Series)
: Ø12.7 mm
(RAS-16G2KVP Series)
One
each
B
Pipe insulating material
(polyethylene foam, 6 mm thick)
1
C
Putty, PVC tapes
One
each
Optional Installation Parts
Insulate the refrigerant pipes separately
with insulation, not together.
2
3
6
4
Insert the cushion between the indoor
unit and wall, and tilt the indoor unit for
better operation.
For the rear left and left piping
Wall
Make sure to run the drain hose sloped
downward.
Do not allow the drain hose to get slack.
Cut the piping
hole sloped
slightly.
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Right
Rear
right
Bottom
right
Rear
left
Bottom left
Left
1
Batteries
Flat head
wood screw
Remote control holder
Vinyl tape
Apply after carrying
out a drainage test.
Wireless remote control
Saddle
Extension
drain hose
(Not available,
provided by installer)
Shield pipe
(Attach to the front panel.)
Air lter
Hook
Installation
plate
Hook
52 mm or more
190 mm or more
225 mm or more
600 mm or more
100 mm or more
100 mm or more
600 mm or more
600 mm or more
Remark :
Detail of accessory and installation parts can
see in the accessory sheet.
Some pictures might be different from the
actual parts.
Drain outlet
Air inlet
Air outlet
125 mm
108 mm
Ø25 mm
29 mm
330 mm
106 mm
121 mm
99 mm600 mm
* Drain nipple and
cap water proof are
packed in outdoor
unit.
6 mm thick heat resisting
polyethylene foam
Bush body
1115751104-EN.indd 31115751104-EN.indd 3 5/26/2557 BE 10:45 AM5/26/2557 BE 10:45 AM