4-8. Outdoor Unit (RAS-10UA-E4, RAS-10UAX4)
No. Parts name Type Specifications
Output (Rated) 750 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor RM5510GNE94 Winding resistance (W) C-R C-S
(at 20°C) 3.710 4.099
Output (Rated) 20 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
2 Fan motor (for outdoor)
HF-240-20B or
Winding resistance (W) Red-Black White-Black
(at 20°C)
387.3 or 235.2
466.2 or 260.1
3
Running capacitor
DS451155BPQC AC 450 V, 1.5 F
(for fan motor)
4
Running capacitor
DS371256CPNB AC 370 V, 25 F
(for compressor)
4-7. Outdoor Unit (RAS-13UAX4, RAS-12UAX4)
No. Parts name Type Specifications
Output (Rated) 1100 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor Winding resistance (W) C-R C-S
(at 20°C) 2.35 3.22
Output (Rated) 30 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
2 Fan motor (for outdoor) HF-240-30B Winding resistance (W) Red-Black White-Black
(at 20°C) 245 388
3
Running capacitor
DS451155BPQC AC 450 V, 1.5 F
(for fan motor)
4
Running capacitor
DS371356CPNB AC 370 V, 35 F
(for compressor)
m
m
m
m
PH225X2C-4FT
SKF-240-20B
FILE NO. SVM-05001
5
Overload relay
LPAP960B
U/T : 6.1A (80°C), OPEN : 135±5°C, CLOSE : 78±11°C