17
FILE NO. SVM-03001
Heat exchanger
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
1.5x500S
PA150X2T-4FM1
Cooling
Mark( )means check points of Gas Leak.
O.D.:12.7mm O.D.:6.35mm
Cooling
Packed valve
(12.7)
Packed valve
(6.35)
0.39m
(Connecting pipe)
12.7
0.49m
(Connecting pipe)
6.35
T1
P
Refrigerant
R410A : 0.97 kg.
5-3. RAS-13UKP-ES2 / RAS-13UA-ES2
RAS-13UKP-AS2 / RAS-13UA-AS2
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.90 9.0 High 27/19 35/24
Cooling Overload 1.10 13.0 High 32/23 43/26
Low temperature 0.70 2.0 Low 21/15 21/15
Fan speed
(indoor)
50Hz
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)