Floor standing indoor unit with DC fan motor
14
Indoor
Unit size
(kW)
Outdoor temperature
(℃DB)
Indoor temperature (℃WB/DB)
14/20 16/23 18/26 19/27 20/28 22/30 24/32
TC SC TC SC TC SC TC SC TC SC TC SC TC SC
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
8.0
20.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.4 9.4 5.5 9.6 5.2
21.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.4 9.4 5.5 9.4 5.1
23.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.4 9.4 5.5 9.4 5.1
25.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.4 9.4 5.5 9.3 5.0
27.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.4 9.1 5.3 9.2 5.1
29.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.5 9.0 5.3 9.1 5.0
31.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.5 8.9 5.2 8.8 4.8
33.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.5 8.8 5.2 8.8 4.8
35.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.4 5.5 8.6 5.1 8.6 4.8
37.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.3 5.4 8.4 5.0 8.6 4.9
39.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.1 5.3 8.3 5.0 8.6 4.9
42.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.1 5.3 8.3 5.0 8.6 4.9
44.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.1 5.3 8.3 5.0 8.6 4.9
46.0 5.5 4.4 6.6 4.9 7.5 5.3 8.0 5.5 8.1 5.3 8.3 5.0 8.6 4.9