7.3 Convertible - EN
Safety Precautions
1 . Applicable ambient temperature range:
lndoor temperature
max. DB/WB
min. DB/WB
32/23 °C
18/14 °C
Cooling
max. DB/WB
46/24 °C
Outdoor temperature
min. DB/WB
18 °C
max. DB/WB
27 °C
lndoor temperature
min. DB/WB 15 °C
Heating
max. DB/WB
24/18 °C
Outdoor temperature
min. DB/WB
-15 °C
2 . If the supply cord is damaged, it must be replaced by the anufacturer or its service agent or a similar qualified
person .
3 . If the fuse on PC coard is broken please change it with the type of T 3 .15A/250VAC .
4 . The wiring method should be in line with the local wiring standard .
5 . The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be
no less than 3mm . Such means for disconnetion must be incorporation in the fixed wiring .
6 . The installation heigh of the indoor unit is recommended from 2 .5m to 2 .7m .
7 . The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m . If
exceeded, the diameter of the wire should be enlarged according to the local wired standard .
8 . The waste battery shall be disposed properly .
9 . We can get 4 different ESP through adjust the indoor unit .
PCB SW1-4 and SW1-5, please refer below:
SW01
Static
pressure
Model
[1] [2] [3] [4] [5] [6] [7] [8]
-- -- -- 0 0 -- -- -- 0Pa
4MXD6512G1000AA
4MXD6518G1000AA
4MXD6524G1000AA
-- -- -- 0 1 -- -- -- 10Pa
-- -- -- 1 0 -- -- -- 20Pa
-- -- -- 1 1 -- -- -- 30Pa
-- -- -- 0 0 -- -- -- 10Pa
4MXD6536G1000AA
4MXD6548G1000AA
4MXD6560G1000AA
-- -- -- 0 0 -- 1 -- 30Pa
-- -- -- 0 0 -- 1 -- 50Pa
-- -- -- 0 0 -- 1 --
70Pa
Attention:cut out the power supply to adjust the SW1-4, and SW1-5, or else the operation is invalid