6 . Capacity compensation rate for pipe length and height defference
4TXK6512G1000AA cooling
Pipe length (m)
5 7.5 10 20 30
Height
difference
(m)
Indoor unit is
upper than
outdoor unit
10
0.980 0.956 0.933
7.5 0.990 0.984 0.960 0.937
5 1.000 0.994 0.988 0.964 0.940
0 1.008 1.002 0.996 0.972 0.948
Indoor unit
is lower than
outdoor unit
-5 1.008 1.002 0.996 0.972 0.948
-7.5 1.002 0.996 0.972 0.948
-10
0.996 0.972 0.948
4TXK6512G1000AAheating
Pipe length (m)
5 10 15 20 30
Height
difference
(m)
Indoor unit is
upper than
outdoor unit
10
0.978 0.968 0.957
7.5 0.988 0.978 0.968 0.957
5 1.005 0.988 0.978 0.968 0.957
0 1.003 0.988 0.978 0.968 0.957
Indoor unit
is lower than
outdoor unit
-5 0.998 0.988 0.978 0.968 0.957
-7.5 0.983 0.973 0.963 0.952
-10
0.971 0.961 0.950
5 4