EasyManua.ls Logo

Trane 4TXK6524G1000AA - 8.2 Indoor Unit Dip Switch Settings (4 MXC6518 G1000 AA)

Trane 4TXK6524G1000AA
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.2 Indoor unit dip switch setting
Model: 4MXC6518G1000AA
PCB CODE: 0151800244AF
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
Description
OFF
ON
OFF -- -- -- -- --
4MXC6518G1000AA
-- -- -- OFF -- -- -- --
Room card unavaible( default)
-- -- --
ON
-- -- -- --
Room card avaible
-- -- -- -- OFF -- -- --
Heating pump( default)
-- -- -- --
ON
-- -- --
Cooling only
-- -- -- -- -- OFF -- --
Fresh air available(default)
-- -- -- -- --
ON
-- --
Fault alarm available
-- -- -- -- -- -- OFF --
Filter remind unavailable(default)
-- -- -- -- -- --
ON
--
Filter remind available
-- -- -- -- -- -- -- OFF
USA region
-- -- -- -- -- -- --
ON Non-USA region(default)
SW3(1-ON,0-OFF)
Decription
SW3
-
1
SW3
-
2
SW3
-
3
SW3
-
4
OFF
OFF
OFF
OFF
Reserve
SW3(1-ON,0-OFF)
indoor unit address No. in group controller
SW3
-
5
SW3
-
6
SW3
-
7
SW3
-
8
OFF OFF OFF OFF
0#(master unit)
OFF
OFF
OFF
ON 1#(slave unit)
OFF
OFF
ON
OFF
2#(slave unit)
OFF OFF
ON ON 3#(slave unit)
OFF
ON
OFF
OFF
4#(slave unit)
OFF
ON
OFF
ON 5#(slave unit)
OFF
ON ON
OFF
6#(slave unit)
OFF
ON ON ON 7#(slave unit)
ON
OFF
OFF
OFF
8#(slave unit)
ON
OFF
OFF
ON 9#(slave unit)
ON
OFF
ON
OFF
10#(slave unit)
ON
OFF
ON ON 11#(slave unit)
ON ON
OFF
OFF
12#(slave unit)
ON ON
OFF
ON 13#(slave unit)
ON ON ON
OFF
14#(slave unit)
ON ON ON ON 15#(slave unit)
121