EasyManua.ls Logo

Trane 4TXK6524G1000AA - 8.2 Indoor Unit Dip Switch Settings (4 MXD6536 G-4 MXD6560 G Series)

Trane 4TXK6524G1000AA
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model: 4MXD6512G1000AA 4MXD6518G1000AA AD24SS1ERC
PCB CODE:0151800267E
Model: AD36NS1ERC 4MXD6548G1000AA AD48HS1ERC
PCB CODE:0151800106G
SW01(1-ON,0-
OFF)
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
Description
ON
OFF OFF -- -- -- -- --
4MXD6512G1000AA
OFF OFF
ON
-- -- -- -- --
4MXD6518G1000AA
ON ON
OFF -- -- -- -- --
4MXD6524G1000AA
-- -- -- OFF
-- -- --
Room card unavaible( default)
-- -- --
ON
-- -- --
Room card avaible
-- -- -- -- OFF -- -- --
Heating pump( default)
-- -- -- --
ON
-- -- --
Cooling only
-- -- -- -- -- OFF -- --
Fresh air available(default)
-- -- -- -- --
ON
-- --
Fault alarm available
--
--
--
--
--
--
OFF
Filter remind unavailable(default)
-- -- -- -- -- --
ON
Filter remind available
-- -- -- -- -- --
OFF
USA region
-- -- -- -- -- --
ON Non-USA region(default)
For 4MXD6512G1000AA 4MXD6518G1000AA 4MXD6524G1000AA, SW03 dip switch setting as below:
SW3-1 SW3-2 SW3-3 SW3-4
Description
OFF
--
--
--
swing motor QTY:1 (default)
--
OFF
--
--
Reverse
--
--
OFF
--
Reverse
--
--
-- OFF
Static pressure level: 4 (default)
--
--
--
ON Reverse
SW03(1
-
ON,0
-
OFF)
Indoor unit address No.in group controller
SW3-5 SW3-6 SW3-7 SW3-8
OFF
OFF
OFF
ON 1#(slave unit)
OFF
OFF
ON
OFF
2#(slave unit)
OFF OFF
ON ON 3#(slave unit)
OFF
ON
OFF OFF
4#(slave unit)
OFF
ON
OFF
ON 5#(slave unit)
OFF
ON
ON
OFF
6#(slave unit)
OFF
ON ON ON 7#(slave unit)
ON
OFF
OFF
OFF
8#(slave unit)
ON
OFF OFF
ON 9#(slave unit)
ON
OFF
ON
OFF
10#(slave unit)
ON
OFF
ON ON 11#(slave unit)
ON ON
OFF OFF
12#(slave unit)
ON ON
OFF
ON 13#(slave unit)
ON ON ON
OFF
14#(slave unit)
ON ON ON ON 15#(slave unit)
124

Related product manuals