(4) Selection of installation location of outdoor With consent from the user, installation location shall:
Be sufficient to bear weight of the units, with air circulation .
Avoid direct radiation from heat sources or other heat sources .
Facilitate the drainage of condensate . Holes in wall shall also facilitate drainage .
Be such that noise and heat air will not disturb neighbors .
Be free of heavy snow in winter .
Allow air inlets and outlets to be free of barriers .
Not allow air outlet to directly face strong airflow .
Facilitate installation at four corners, with 1m space above the unit .
Be convenient for maintenance and repair .
For installation of multiple units, sufficient space shall be ensured to avoid short circuit .
The air conditioner shall not be mounted on a non-dedicated metal frame (e .g . burglar mesh) .
When the outdoor unit is installed on a street side, its height shall not be less than 2 .5m
6 2
Model H
4MXC6518G1000AA 260
4MXC6524G1000AA
4MXC6536G1000AA
246
4MXC6548G1000AA
4MXC6560G1000AA
288
Space required for installation (unit: mm)
More than 2500 above the
ground
>
1500
1000
Outlet Suction inlet
Outlet
> 1500
> 1500
1500
> 1500
1500