26
18-BB41D1-1C-EN
Figure 10. 4WCC4036E1
Cooling Heating
DISCHARGE PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
SUCTION PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
COOLINGPERFORMANCECAN BE CHECKED WHEN THEOUTDOOR TEMP IS ABOVE65 DEG F.
TOCHECK COOLING PERFORMANCE, SELECT THEPROPER INDOOR CFM, ALLOW PRESSURES TOSTABILIZE.
MEASUREINDOOR WET BULB . TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGEAND SUCTION PRESSURES.
ON THEPLOTS LOCATEOUTDOOR TEMPERATURE (1); LOCATEINDOOR WET BULB (2)
FIND INTERSECTION OFOD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION PRESSUREIN LEFT; COLUMN (4).
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION ACTUAL:
(4) DISCHARGEPRESSURE@1050 CFM CFM IS 324 PSIG. DISCHARGEPRESSURE SHOULD BE+/- 10 PSI OFCHART
(5) SUCTION PRESSURE@1050 CFM CFM IS 141 PSIG. SUCTION PRESSURESHOULD BE+/- 3 PSIGOFCHART
DWG.NO.
4WCC4036E1
110
115
120
125
130
135
140
145
150
155
160
165
170
40 60 80 100 120
200
250
300
350
400
450
500
40 60 80 100 120
(1)
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59
30
40
50
60
70
80
90
100
110
120
130
140
-5 5 15 25 35 45 55 65
200
225
250
275
300
325
350
375
400
425
450
475
500
-5 5 15 25 35 45 55 65
INDOOR ENTERING
DRY BULB CURVES
TOP TO BOTTOM
80, 70, AND 60 DEG F.
INDOOR ENTERING
DRY BULB CURVES
TOP TO BOTTOM
80, 70, AND 60 DEG F.
UUnniitt SSttaarrttuupp