Performance
Data
CAB-PRC001-EN20
Hot Water
Coils
Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (-1 C)
T. All performance measured on high speed tap, zero ESP, and a throwaway filter.
Table PD-4. Free Discharge Motor, Group 3
Heating
Unit CFM TMBH GPM WPD 115V 230V 277V
Size Coil (L/s) (TkW) Q/ITD (L/s) (kPa) Watt Watt Watt
2 2 H 198 (93) 13.8 (4.1) 0.13 0.92 (0.06) 3.8 (11.3) 6 0 9 5 65
3 H 188 (90) 16.7 (4.9) 0.15 1.11 (0.07) 8.0 (23.8) 6 0 9 5 65
4 H 177 (84) 17.3 (5.1) 0.16 1.16 (0.07) 2.2 (6.4) 6 0 95 6 5
3 2 H 262 (124) 18.3 (5.4) 0.17 1.22 (0.08) 6.9 (20.6) 7 0 8 0 83
3 H 260 (123) 22.1 (6.5) 0.20 1.47 (0.09) 2.9 (8.7) 8 5 89 101
4 H 242 (114) 23.7 (6.9) 0.22 1.58 (0.10) 4.1 (12.3) 8 5 8 9 101
4 2 H 330 (156) 22.8 (6.7) 0.21 1.52 (0.10) 2.6 (7.7) 9 5 9 6 104
3 H 320 (151) 28.1 (8.2) 0.26 1.87 (0.12) 5.1 (15.2) 100 107 106
4 H 304 (144) 30.3 (8.9) 0.28 2.02 (0.13) 7.3 (21.9) 100 107 106
6 2 H 512 (242) 35.8 (10.5) 0.33 2.38 (0.15) 7.0 (21.0) 110 154 165
3 H 508 (240) 43.3 (12.7) 0.39 2.88 (0.18) 3.3 (9.7) 125 130 124
4 H 483 (228) 47.2 (13.8) 0.43 3.14 (0.20) 4.4 (13.3) 125 130 124
8 2 H 665 (314) 45.0 (13.2) 0.41 3.00 (0.19) 3.2 (9.4) 135 150 159
3 H 623 (294) 54.3 (15.9) 0.49 3.62 (0.23) 5.5 (16.3) 120 123 133
4 H 596 (282) 59.2 (17.3) 0.54 3.94 (0.25) 7.5 (22.4) 120 123 133
1 0 2H 829 (391) 57.5 (16.9) 0.52 3.83 (0.24) 5.5 (16.3) 205 250 269
3 H 835 (394) 72.9 (21.3) 0.66 4.86 (0.31) 10.5 (31.2) 225 237 230
4 H 796 (376) 79.0 (23.1) 0.72 5.26 (0.33) 14.4 (42.9) 225 237 230
1 2 2H 940 (444) 66.5 (19.5) 0.60 4.43 (0.28) 7.6 (22.8) 230 246 263
3 H 923 (436) 80.6 (23.6) 0.73 5.37 (0.34) 8.2 (24.6) 220 230 239
4 H 876 (413) 87.9 (25.8) 0.80 5.86 (0.37) 9.4 (28.2) 220 230 239
Note:
1. CFM = Cubic feet per minute
2. TMBH = Total capacity (MBH)
3. GPM = Gallons per minute
4. WPD = Water pressure drop (feet of water)
5. Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when DT and GPM (L/s) remain constant. To determine heating capacities at a different entering water
temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
6. Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.