CDHF-SVU01C-EN
34
Operator
Interface
Reference
Top Level Mode Sub Level Mode BAS Code
SYSTEM RESET Boot & Application software part number, self-test, and
configuration validity screens will be present. NA
Stopped Local Stop 00
Stopped Panic Stop 00
Stopped Diagnostic Shutdown – Manual Reset 00
Run Inhibit Ice Building Is Complete 100
Run Inhibit Tracer Inhibit 100
Run Inhibit External Source Inhibit 100
Run Inhibit Diagnostic Shutdown – Auto Reset 100
Auto Waiting For Evaporator Water Flow 58
Auto Waiting For A Need To Cool 58
Auto Waiting For A Need To Heat 58
Auto Power Up Delay Inhibit: MIN:SEC 58
Waiting To Start Waiting For Condenser Water Flow 70
Waiting To Start Establishing Oil Pressure 70
Waiting To Start Pre-Lubrication Time: MIN:SEC 70
Figure 23