4. Variable speed compressor.
a. Override compressor 1 ON.
b. Override circuit 1 to 0%.
c. Override HGRH to 100%.
d. Maintain head pressure 400 psi.
e. Record electrical data, refrigerant pressures, saturated
temperature and line temperature on horizon. Start-Up
sheet (available at the end of this document).