Table 8. Menu descriptions
Screen Menu Point List Min/Inactive Default Max/Active
BAS
Point?
Alarms
Active Alarms List of all active alarms
All Alarms List of all previous alarms
Reports
(continued
on next
page)
Custom Graphics *NOT USED*
System Status
Program Control Discharge Air Control Space ControlSpace ControlY
Heat Cool Mode Active Heat — Cool N
Occupancy Status Occupied|Unoccupied|Occupied Bypass|Occupied Standby|Unknown Y
Compressor 1 Command Off — On N
Compressor 2 Command Off — On N
Compressor 3 Command Off — On N
Compressor 4 Command Off — On N
Digital Scroll Command 0% — 100% N
Dehumidification Command Disabled Enabled N
Discharge Air Temperature Local Analog Input
Economizer Mode Disabled Enabled N
Evap Leaving Temp Local Analog Input
Heat Capacity 0% — 100% N
Heating Output Command 0% — 100% N
Heat 1 Command Off — On N
Heat 2 Command Off — On N
Heat 3 Command Off — On N
Inducer Command Off — On N
Gas Valve Status Binary Input
HGRH Command 0% — 100% N
OA Damper End Switch Binary Input
Outdoor Air Damper Command Closed — Open N
OAD Position Local Binary Input
Outdoor Air Relative Humidity Local Analog Input
Outdoor Air Temperature Local Analog Input
Space Dewpoint Active Analog Input
Space Temperature Local Analog Input
Supply Fan Start Stop Command Off — Off N
Filter Status Clean — Dirty N
System Lockout Normal Normal Lockout N
UNOCC Cooling Mode Off — On N
UNOCC Dehumid Mode Off — On N
UNOCC Heating Mode Off — On N
ERV Command Disable — Enable N
ERV Leaving Air Temperature Local Analog Input
PEVFD Command 0% 80% 100% Y
Discharge Airflow Local Analog Input
ERV Leaving Air Humidity Local Analog Input
Circuit 1 Reversing Valve
(a)
Disabled — Enabled N
Circuit 2 Reversing Valve(a) Disabled — Enabled N
Condenser Fan Command(a) Disabled — Enabled N
OAD Position Command 0% — 100% N