Installation
OAU-SVX01H-EN 33
DC Conductors
Factory-Provided Sensors
A discharge temperature sensor (VELSEN-0021) will be
factory-provided for field installation in the supply duct.
Refer to Figure 50, p. 69 for installation instructions.
If space control is selected, a combination space
temperature/humidity sensor (BAYSENS036A) will be
factory-provided for field installation in the space. Refer to
Figure 51, p. 70 for installation instructions.
If multi-zone VAV control is selected, a static pressure
sensor (VELCON-0350) will be factory-provided for field
installation in the supply duct or space. Refer to Figure 53,
p. 72 for installation instructions.
If modulating OA/RA dampers w/economizer and an
exhaust fan are selected, a duct static pressure sensor
(VELCON-0350) will be factory-provided for field
installation in the return duct. Refer to Figure 53, p. 72 for
installation instructions.
Table 7. Zone sensor module wiring
Distance from Unit to Control Recommended Wire Size
000–150 feet
0–45.7 m
22 gauge
0.33 mm
2
151–240 feet
46–73.1 m
20 gauge
0.50 mm
2
241–385 feet
73.5–117.3 m
18 gauge
0.75 mm
2
386–610 feet
117.7–185.9 m
16 gauge
1.3 mm
2
611–970 feet
186.2–295.7 m
14 gauge
2.0 mm
2
Figure 31. OAUTS connection B