RT-SVX074A-EN
25
Clearances
Figure 24, p. 25 illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged unit
capacity, and peak operating efficiency. Providing less than
the recommended clearances may result in condenser coil
starvation, “short-circuiting” of exhaust and economizer
airflows, or recirculation of hot condenser air.
Figure 24. Typical installation clearances for single and multiple unit applications
Side by Side
Note 1
End to End
Note 1, 2
7’0”
2134 MM
6’0”
1829 MM
3’0”
914 MM
Single Unit
3’0”
914 MM
3’0”
914 MM
4’0”
1219 MM
Notes:
1. When equipped with economizer
or barometric relief damper, clearance
distance is to be measured from
protruding hood instead of base.
2. Clearance is the same if any unit
is rotated 180 degrees.
4’0”
1219 MM
for D cabinet
5’0”
1525 MM
for D cabinet
5’8” for D cabinet
1727 MM
Weights
Table 1. Model weights, corner weights (lbs) and center of gravity dimensions (in.)
Tons Unit Model No.
Model Weights
(a)
Corner Weights
(b)
Center of Gravity (in.)
Shipping
Net A B C D
Length
Width
6 THJ072 1007 909 298 278 160 172 43 19
7.5 THJ090 1011 913 300 280 161 172 43 19
8 THJ102 1027 929 305 285 164 176 43 19
10 THJ120 1037 939 308 288 165 177 43 19
12.5 THJ150 1412 1218 356 360 252 250 50 26
15 THJ180 2040 1820 611 447 322 440 52 36
17.5 THJ210 2070 1850 612 463 334 441 53 36
20 THJ240 2140 1920 689 472 309 451 50 34
25 THJ300 2190 1970 684 484 332 469 51 35
(a)
Weights are approximate. Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights to be added to unit weight,
reference the following table.
(b)
Corner weights are given for information only.
Dimensions and Weights