Pub. No. 22-1840-14
TUHM AIRFLOW - COOLING
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
CFM
504 565 586 521 540
Watts
34 70 104 138 172
CFM
547 604 624 559 579
Watts
40 77 112 147 182
CFM
590 644 663 597 617
Watts
47 85 121 157 193
CFM
656 695 701 703 694
Watts
54 93 130 167 204
CFM
676 724 740 674 694
Watts
62 102 140 179 217
CFM
764 792 801 795 789
Watts
75 116 157 197 238
CFM
806 844 856 788 810
Watts
89 133 175 216 259
CFM
877 899 901 895 886
CFM
660 709 726 659 680
Watts
59 99 136 174 212
CFM
740 768 772 769 764
Watts
70 109 149 189 229
CFM
768 809 822 755 776
Watts
81 123 164 205 246
CFM
848 869 871 868 858
Watts
94 138 179 220 265
CFM
875 909 918 850 872
Watts
107 153 197 240 284
CFM
978 994 992 989 980
Watts
130 179 224 270 316
CFM
1037 1058 1063 994 1017
Watts
157 209 258 305 354
CFM
1093 1096 1082 1065 1051
CFM
816 854 865 798 819
Watts
92 136 178 220 262
CFM
881 914 923 855 877
Watts
108 155 199 242 286
CFM
945 974 981 912 935
Watts
127 176 222 266 313
CFM
1029 1043 1043 1035 1028
Watts
148 199 246 292 340
CFM
1074 1093 1097 1027 1050
Watts
170 224 274 322 372
CFM
1170 1181 1184 1180 1174
Watts
206 262 317 370 423
CFM
1268 1276 1270 1199 1224
Watts
254 314 372 430 484
CFM
1321 1321 1306 1295 1251
CFM
972 998 1005 936 959
Watts
135 185 232 277 324
CFM
1047 1068 1073 1003 1026
Watts
161 213 262 310 359
CFM
1123 1138 1140 1070 1094
Watts
189 244 296 347 398
CFM
1195 1204 1208 1205 1195
Watts
215 275 329 383 437
CFM
1273 1278 1275 1204 1228
Watts
257 317 376 433 488
CFM
1375 1385 1384 1383 1305
Watts
316 383 444 513 513
CFM
1499 1487 1491 1392 1303
Watts
389 457 513 513 513
CFM
1513 1512 1508 1418 1341
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
*UHMB080ACV3VB^ Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter