Table 14. VPxF 05SQ ECM CFM (continued)
Airflow
(Min CFM: 280,
Max CFM: 1850)
Trane
Controller
PWM Signal
(a)
ECM Control Board
Signal
(b) (c)
CFM
L/s
% Setting
0-10V 2-10V
908 428 40% 4.0 5.2
986 466 45% 4.5 5.6
1065 503 50% 5.0 6.0
1144 540 55% 5.5 6.4
1222 577 60% 6.0 6.8
1301 614 65% 6.5 7.2
1379 651 70% 7.0 7.6
1458 688 75% 7.5 8.0
1536 725 80% 8.0 8.4
1615 762 85% 8.5 8.8
1693 799 90% 9.0 9.2
1772 836 95% 9.5 9.6
1850 873 100% 10.0 10.0
(a)
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
(b)
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
(c)
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 15. VPxF 06SQ ECM CFM
Airflow
(Min CFM: 530,
Max CFM: 2100)
Trane
Controller
PWM Signal
(a)
ECM Control
Board Signal
(b) (c)
CFM
L/s
% Setting
0-10V 2-10V
530 250 0% 0.0 2.0
609 287 5% 0.5 2.4
687 324 10% 1.0 2.8
766 361 15% 1.5 3.2
844 398 20% 2.0 3.6
923 435 25% 2.5 4.0
1001 472 30% 3.0 4.4
1080 509 35% 3.5 4.8
1158 546 40% 4.0 5.2
1237 584 45% 4.5 5.6
1315 621 50% 5.0 6.0
1394 658 55% 5.5 6.4
1472 695 60% 6.0 6.8
1551 732 65% 6.5 7.2
1629 769 70% 7.0 7.6
1708 806 75% 7.5 8.0
Table 15. VPxF 06SQ ECM CFM (continued)
Airflow
(Min CFM: 530,
Max CFM: 2100)
Trane
Controller
PWM Signal
(a)
ECM Control
Board Signal
(b) (c)
CFM
L/s
% Setting
0-10V 2-10V
1786 843 80% 8.0 8.4
1865 880 85% 8.5 8.8
1943 917 90% 9.0 9.2
2022 954 95% 9.5 9.6
2100 991 100% 10.0 10.0
(a)
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
(b)
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
(c)
ECM control board with 2-10 VDC, has combined fan on/off and
modulation input where fan comes on when signal rises to 2 VDC and
goes off when signal falls to 1 VDC.
Table 16. VSxF 03SQ ECM CFM
Airflow
(Min CFM: 200,
Max CFM: 1100)
Trane
Controller
PWM Signal
(a)
ECM Control Board
Signal
(b) (c)
CFM
L/s
% Setting
0-10V 2-10V
200 94 0% 0.0 2.0
245 116 5% 0.5 2.4
290 137 10% 1.0 2.8
335 158 15% 1.5 3.2
380 179 20% 2.0 3.6
425 201 25% 2.5 4.0
470 222 30% 3.0 4.4
515 243 35% 3.5 4.8
560 264 40% 4.0 5.2
605 285 45% 4.5 5.6
650 307 50% 5.0 6.0
695 328 55% 5.5 6.4
740 349 60% 6.0 6.8
785 370 65% 6.5 7.2
830 392 70% 7.0 7.6
875 413 75% 7.5 8.0
920 434 80% 8.0 8.4
965 455 85% 8.5 8.8
1010 477 90% 9.0 9.2
1055 498 95% 9.5 9.6
1100 519 100% 10.0 10.0
(a)
% setting from Trane unit controller via pulse width modulating
signal or ECM control board with manual fan speed adjust setting.
(b)
ECM control board with 0-10 VDC fan modulation input and separate
fan on/off binary input required.
UUnniitt SSeettuupp