EasyManua.ls Logo

Trane VUV 1500 CFM - Page 20

Trane VUV 1500 CFM
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 UV-SVN03D-EN
Modulating Water Valves (Option)
The actuator on the valve is a 24V, 3-
point floating valve. The actuator can
be easily removed from the valve body
by pressing in on the locking tab and
rotating the actuator 45° counter-
clockwise (See Figure 6a). The 2-way
valves are bi-directional flow. The 3-
way valves can be mixing or diverting
(See Figure 6b).
Note: The actuator must be removed if
soldering is being conducted near the
valve. High heat may cause damage to
the actuator’s plastic body/mecha
-
nisms.
Figure 6a: Remove modulating valve
actuator by pressing in tab (inset) and
turning actuator 45° counterclockwise.
Figure 6b: Steam piping
On applications without the optional,
factory installed piping packages, it is
important to remove the cartridge as
-
sembly from the valve body with the
provided tool (Figure 7).
Figure 7: Cartridge removal tool
Closed
Open
A
B
A
B
AB<->B
AB
B
AB<->A
A
AB
2-way valve
3-way valve
Use the following steps to complete
cartridge assembly removal:
1 Remove valve actuator.
2 Remove the cartridge assembly
from the valve body with the en-
closed tool.
3 Solder the valve in accordance with
normal soldering practices.
4 Re-install the cartridge after solder-
ing by tightening until it bottoms
out. The top surface of the car-
tridge will be flush with the top
edge of the body casting.
Note: Do not overtighten. Maxi-
mum torque is 40 in-lb.
5 Replace valve actuator and wire in
accordance with instructions.
Plumbing the Valve
The valve may be plumbed in any an-
gle but preferably not with the actua-
tor below horizontal level of the body.
Make sure there is enough room
around the actuator for servicing or re
-
placement.
For use in diverting applications, the
valve is installed with the flow water
entering through the bottom AB port
and diverting through end ports A or
B. In mixing applications the valve is
installed with inlet to A or B and outlet
through AB.
Mount directly to the tube or pipe. Do
not grip the actuator while making or
tightening plumbing connections. Ei
-
ther hold valve body by hand or attach
an adjustable spanner (38mm/1-1/2”)
across the hexagonal or flat faces on
the valve body. See Figure 8.
Figure 8: Proper plumbing technique
for modulating valves
Installation