Specifications
6 BAS-SVU040G-EN
Clock, Schedule, Setpoints, and Options
Clock
Defines the time and date used with the programmable time schedule
function:
Tim
e format:
AM-PM: 12 hour format. (Displays as 8:00 PM)
24 Hours: 24 hour format. (Displays as 20:00 hours)
Time – defines the hour and minute of the current day.
Year – defines the current year.
Month – defines the current month.
Day – defines the current day of the month.
Weekday – displays a day of the week corresponding to the date
entered into the sensor.
Schedule
Defines the time values that are used to determine when to transition
from the current occupancy state to the next state.
Three occupied/unoccupied event pairs are supported. Setting an event
to a time value enables the event. Setting the event to - - : - - disables the
event.
Setpoints
Defines the following:
Unocc. cool – the temperature setpoint in use when the equipment is
in cooling mode and
occupancy mode is unoccupied.
Occ. cool – the temperature setpoint in use when the equipment is in
cooling mode and occ
upancy mode is occupied.
Occ. heat – the temperature setpoint in use when the equipment is in
heating mode and o
ccupancy mode is occupied.
Unocc. heat – the temperature setpoint in use when the equipment is
in heating mode and occupancy mode is unoccupied.
(50.0°F to 90.0°F [10.0°C to 32.2°C])
Options
Defines the occupancy commands and schedule type.
Occupancy cmd
Loc. occ.: occupancy is determined by the schedule.
Occupied: force occupied mode.
Unocc.: force unoccupied mode.
Schedule type
7 days: each day of the week.
5+2: weekdays + weekend.
5+1+1: weekdays + Saturday + Sunday.
Specifications
Sensor Operating
Temperature
32°F to 122°F (0°C to 50°C)
Storage
Temperature
- 22°F to 122°F (- 30°C to 50°C)
Storage and
Operating
Humidity Range
0% to 95%, non-condensing
Temperature
Control Accuracy
+/- 0.9°F (+/- 0.5°C) @ 70F (21°C) typical calibrated
Temperature
Sensor Resolution
+/- 0.2°F (+/- 0.1°C)
Room Air
Temperature
Display Range
- 40°F to 122°F (- 40°C to 50°C)