Humidty Settings
2). When the Device 1 is selected, user can set the humidity setpoint for Day/ Night mode for the Device 1.
The unit will automatically turn ON the Humid Device 1 when the measured humidity is ABOVE or BELOW
the setpoint.
Press ENTER button and the Above or Below text will be flashing.
Press UP or DOWN button to change between Above and Below.
Finally, press ENTER button to confirm and save the change. The LCD screen will display “Setting saved".
For example: Turn on device when humidity level is Above setpoint for Dehumidifier; Turn on device when
humidity level is Below setpoint for Humidifier. Use UP and DOWN button to select Day mode or Night mode,
the selected item will be highlighted. Press ENTER button and the current Humid value will be flashing.
Press UP or DOWN button to change the setpoint. Finally, press ENTER button to confirm and save the
change. The LCD will display “Setting saved".
1). On the Setting page, select the Humid subject and then press ENTER button to access the Humid
setting page. Use the Up button or Down button to select the Device 1 or Device 2 or Alarm setting.