102417
60 Hz
Automatic pump control
Code
Description
Voltage
Frequency
16 A
Current
1118 W (1.5Hp)
For pumps up to
The power cable has cable clamps type: Y
The construction class of the tool is: Basic insulation.
The thermal insulation class of the motor wiring is: Class B
Power requirements
127 V
1”
Input and output diameter
Water maximum temperature
50 min of work and 20 min of rest. Maximum 6 hours per day.
18 AWG x 3C with insulation temperature of 221 °F
Conductors
Work cycle
Class I
Insulation
de 1.75 bar (25 PSI) a 3.5 bar (51 PSI)
140 °F
Working pressure
10 bar (145 PSI)
Maximum operating pressure
Connection to the power supply must be made by an
electrical professional, following the electrical diagram on the right.
Use a separate electrical circuit for the pump. This circuit
must not have conductors with a gauge smaller than 12 AWG, and must be
protected with a 20 A time delay fuse. Before connecting the motor to the
power line, make sure that the voltage is equal to the voltage indicated on the
motor nameplate. Operating at a lower voltage will damage the motor.
The power cords are color-coded as follows:
Green: Ground
White: Neutral
Black: Line
Technical data
ENGLISH
WARNING
WARNING
Avoid the risk of electric shock or severe injury. When the power cable gets damaged
it should only be replaced by the manufacturer or at a Authorized Service Center.
The build quality of the electric insulation is altered if spills or liquid gets into the tool while in use.
Do not expose to rain, liquids and/or dampness.
Before gaining access to the terminals all power sources should be disconnected.
From 0 and up to 10 A
From 10 and up to 13 A
From 13 and up to 15 A
From 15 and up to 20 A
18 AWG
16 AWG
14 AWG
8 AWG
16 AWG
14 AWG
12 AWG
6 AWG
3 (one grounded)
From 6 ft to 49 ft | Higher than 49 ft
Ampere
Capacity
Number of
Conductors
Extension Gauge
When using power tools outdoors use grounded extension cable labeled “Outdoors
Use”. These extension cables are specially manufactured for outdoors use and reduce the risk of electric shock.
WARNING
CAUTION
CAUTION
CAUTION
1 2
V U N L
3 4 5 6
Terminal
board
Line
Line
Ground
Motor
Motor
Ground