F14: Post cleaning mode pause time between solenoid valves (fan off).
Possible values: 001” – 999” step 1”.
Default = 010”.
F15: Maintenance frequency expressed in tens of hours
Possible values: 001 – 999 step 1. (e.g.: 1=10h, 10=100h).
Default = 100 (=1000h).
F16: Maintenance deadline alarm enable.
Possible values: 0 (disabled) – 1 (enabled).
Default = 0 (disabled).
F17: Maintenance hour counter reset.
Possible values: 0 (disabled) – 1 (reset).
Default = 0 (disabled).
Note: The maintenance hour counter
will be reset and the F17 parameter will be set back to 0 by setting F17 to 1.
F18: Precoating function enabling.
Possible values: 0 (disabled) – 1 (enabled).
Default = 0 (disabled).
F19: dP threshold for precoating function.
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 2.00 kPa.
F20: Enabling Minimum dP Alarm function.
Possible values: 0 (disabled) - 1 (enabled).
Default = 0 (disabled).
F21: Min dP Alarm Threshold (Broken Sleeve/Cartridge)
Possible values: 0.00 kPa – 3.99 kPa step 0.01.
Default = 0.20 kPa.
F22: Selection of minutes or hours for Forced Cleaning Cycle.
(Only if the operating mode F01 = 2)
Minutes (0 =minutes, 1 =hours)
Default = 0 (Minutes)
F23: Setting time interval for Forced Cleaning Cycle in relation
to the choice of F22.
Setting values: 1 - 999 step 1.
Default = 240 (240 minutes).
F24: Setting the date on the internal clock.
Settable values: Day 1 – 31 d.
Month 1 – 12 п.
Year 00 – 99 y.
F25: Setting of the time for the internal clock.
Settable values: Hours: 0 – 23 HH.
Minutes: 0 – 59 пп.
F26: Exclusion of the valve in short circuit.
If set to 1 the valve shorted is excluded from the cycle.
Settable Values 0 (not excluded) - 1 (excluding)
Default = 0 (not excluded).