stainless steel ball. When the alloy melts
at its rated temperature, the ball is forced
upward into the center strut, releasing the
two ejectors and operating the sprinkler.
WARNING
The Model H Horizontal Sidewall Sprin-
klers described herein must be installed
and maintained in compliance with this
document, as well as with the applicable
standards of the National Fire Protection
Association, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the integrity of
these devices.
The owner is responsible for maintaining
their fire protection system and devices in
proper operating condition. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Sprinkler Identification Number
SIN C1311 - (K=2.8)
SIN C2311 - (K=4.2)
SIN C3311 - (K=5.6)
Approvals
UL & ULC Listed. FM & NYC Approved
(Refer to Table 1 - 3. The approvals
apply only to the service conditions
indicated in the Design Criteria Section)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT
Discharge Coefficient
K = 2.8 GPM/psi
1/2
(40,3 LPM/bar
1/2
)
K = 4.2 GPM/psi
1/2
(60,5 LPM/bar
1/2
)
K = 5.6 GPM/psi
1/2
(80,6 LPM/bar
1/2
)
Temperature Ratings
165°F/74°C, 212°F/100°C, 286°F/141°C
Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model H
No. 1-4.0
2.8, 4.2, & 5.6 K-factor
Standard Response
Standard Coverage
Horizontal Sidewall Fusible Solder Type Automatic Sprinkler
General
Description
The Central Model H Horizontal Sidewall
Sprinklers are standard response -
standard coverage, fusible solder type
spray sprinklers intended for use in fire
sprinkler systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (e.g., UL Listing is based
on NFPA 13 requirements).
Horizontal Sidewall Sprinklers are
generally used in lieu of pendent & upright
sprinklers because of building construction
or installation economy considerations.
They are designed for installation along a
wall or the side of a beam and just
beneath a smooth ceiling. Installed with
their centerline of waterway parallel to the
ceiling, these sprinklers produce a quarter-
spherical water discharge pattern that is
predominately directed downward &
outward from the deflector; however, a
portion of the spray is also directed
towards the backwall.
These sprinklers are available with wax
and lead coatings that may be utilized to
extend the life of copper alloy sprinklers
beyond that which would otherwise be
obtained when exposed to corrosive
atmospheres.
Although wax and lead coated sprinklers
have passed the standard corrosion tests
of the applicable approval agencies, the
testing is not representative of all possible
corrosive atmospheres. Consequently, it is
recommended that the end user be
consulted with respect to the suitability of
these corrosion resistant coatings for any
given corrosive environment. The effects
of ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
Operation: A fusible alloy is sealed into a
bronze actuating rod (center strut) by a
Technical
Data
CENTRAL
H 2-01
Standard Spray
Horizontal
Sidewall
Sprinklers
Corrosion Resistant Coatings
Sprinkler: Wax, Lead & Wax-over-Lead
Physical Characteristics
The Model H Horizontal Sidewall Sprin-
klers utilize a dezincification resistant
(DZR) bronze frame and a brass deflector.
The waterway is sealed with copper seal
disk, and the fusible assembly is con-
structed of bronze and stainless steel
components.
OBSOLETE
Question and Answer IconNeed help?

Do you have a question about the Tyco Fire Product CENTRAL H and is the answer not in the manual?

Summary

General Description

Operation

Explains how the fusible link releases the ball and ejectors to activate the sprinkler.

Technical Data

Sprinkler Identification Number

Unique identifiers for different K-factors (C1311, C2311, C3311).

Approvals

Certifications from UL, ULC, FM, and NYC.

Maximum Working Pressure

Specifies the maximum operating pressure of 175 psi.

Pipe Thread Connection

Indicates the standard 1/2 inch NPT connection.

Discharge Coefficient

Flow rate coefficients (K-factors) for different sprinkler models.

Temperature Ratings

Available temperature ratings in Fahrenheit and Celsius.

Finishes

Lists available sprinkler finishes like Polyester, Chrome, Brass.

Corrosion Resistant Coatings

Describes options like wax and lead coatings for durability.

Physical Characteristics

Details materials like DZR bronze frame and brass deflector.

Design Criteria

Listing and Approval Details

Specifies UL, ULC, NYC, and FM approvals for different K-factors and hazard types.

Installation Clearances

Defines maximum distances below ceiling and deflector-to-wall dimensions.

Installation

Installation Torque

Recommends torque values for 1/2 inch NPT sprinkler joints.

Installation Steps

Provides sequential steps for proper sprinkler installation.

Care & Maintenance

Maintenance Instructions

Guidance on sprinkler inspection, testing, and general upkeep.

Corrosion and Damage

Advises on handling corrosion, leaks, and physical damage to sprinklers.

System Shutdown Procedures

Outlines steps for safe system shutdown during maintenance.

Limited Warranty

Warranty Terms

Details the 10-year warranty against defects in material and workmanship.

Ordering Information

How to Order

Instructions on specifying product details when placing an order.

Tyco Fire Product CENTRAL H Specifications

General IconGeneral
BrandTyco Fire Product
ModelCENTRAL H
CategoryIrrigation System
LanguageEnglish

Related product manuals