Do you have a question about the Tyco CIM800 and is the answer not in the manual?
Details how to assemble MX800 modules into an ANC-8 ancillary housing.
Instructions for fitting CIM800 modules into an M520 double gang cover, including sealing.
Details how to assemble MX800 modules into an ANC-8 ancillary housing.
Instructions for fitting CIM800 modules into an M520 double gang cover, including sealing.
The CIM800 Contact Input Module is a device designed to monitor fire contacts, such as those found in extinguishing system controls, ventilation controls, and fire door controls. It is compatible with MX Fire Alarm Controllers and is intended for indoor applications only.
The CIM800 complies with:
The CIM800 can be configured in several ways to monitor various types of contacts:
The CIM800 can be installed in an ANC-8 ancillary housing or an M520 double gang cover.
The CIM800 has a default factory set address of 255. This address must be set to the loop address of the device using the 801AP MX Service Tool. Programming can be done either prior to installation using the internal programming port (Fig. 4) or after installation using the programming port on the front cover (Fig. 6).
Cables must be selected according to Publication 17A-02-D and BS5839 requirements. Two pairs of connection terminals (L+ and L-) are provided on the terminal block for connecting the module to the addressable circuit. A maximum of one 1.5mm² or one 2.5mm² cable can be connected at any one terminal.
The module fits onto a standard dual-gang MK box or an ANC8 ancillary housing.
The manual does not explicitly detail maintenance features beyond the initial installation and configuration. However, the ability to program the address after installation and the visual LED indicator for status provide some diagnostic capabilities.
| Brand | Tyco |
|---|---|
| Model | CIM800 |
| Category | I/O Systems |
| Language | English |
Loading...