F3200 Installation & Programming Manual Document No: LT0122
Programming System Configuration
Page 7-34 5 July 2001 Issue 2.7
7.5.3 MODULE RELAY SUPERVISION
This is option 2 of the Relay Supervision menu.
To program module relay supervision the desired relay number is selected by use of the
"NEXT" and "PREV" keys.
The options which may be selected are:
Supervision enabled (E) or disabled (D).
Supervision latching (L) or non-latching (N) (i.e. the fault condition).
Fault and isolate mapped (M) or not mapped to the MAF.
Supervision and relay status mapped to LED n on an LED Display (where fitted).
Isolatable (yes/no)
Testable (yes/no)
Supervise Activated State (yes/no)
The mode of monitoring is always "load" (refer to Sections 3.4.4 and 8.6).
The mapping of the relay status (activated, isolated, fault or normal) to LEDs on an LED
Display is described in Sections 2.3.2 and 7.3.3.