FIRE FIGHTER’S GUIDE
1. VIEW NEXT ALARM
Press "NEXT" key once -
- The LCD will display the next alarm.
2. ACKNOWLEDGE DISPLAYED ALARM
Press "ACK" key once.
- LCD will display "ACKD" for the displayed alarm.
- If all alarms are acknowledged, the ALARM LED will go
steady.
3. RESET ALL ACKNOWLEDGED ALARMS
Press "RESET" key once.
- LCD will display "Resetting all acknowledged alarms".
- If there are no acknowledged alarms the LCD will display "No
acknowledged zones to reset".
- If all alarms are reset, the LCD will exit FFCIF mode.
4. ISOLATE ALL ACKNOWLEDGED ALARMS
Press "ISOLATE" key once.
- LCD will display "Isolating all acknowledged alarms".
- If there are no acknowledged alarms the LCD will display "No
acknowledged zones to isolate".
- Isolated LED will turn on if any zones are isolated.
- If all alarms are isolated, the LCD will exit FFCIF mode.
5. ISOLATE/DE-ISOLATE BELLS
Press "BELLS ISO" key once.
- If the "Bells Isolated" LED is off
The "Bells Isolated" LED will turn on steady.
The bells will turn OFF if they are on.
- If the "Bells Isolated" LED is on.
The "Bells Isolated" LED will turn off.
If any un-isolated alarms exist, the bells will ring.
6. BRIGADE TEST
Press and hold the "BRIG TEST" key for at least 2 seconds.
- The Alarm LED will turn on.
- The FIP will signal Alarm to the brigade, if programmed
to.

Table of Contents

Other manuals for Tyco F3200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco F3200 and is the answer not in the manual?

Tyco F3200 Specifications

General IconGeneral
BrandTyco
ModelF3200
CategoryFire Alarms
LanguageEnglish

Related product manuals