Document No: LT0119 F3200 Operator's Manual
System Specifications
Issue 2.04 29 July 2002 Page 3-9
3.5 OUTPUT SPECIFICATIONS
3.5.1 8 ZONE MODULE OUTPUTS
Type Darlington open collector
Switch to 0V
Voltage Rating 28.5V max, "off" state
1V max @ 30mA, "on" state
1.1V max at 100mA
Current Rating 100mA max per O/P, 1A max per FIP
Operation Programmable
Default O/C 1 = Zone 1 Alarm
O/C 2 = Zone 2 Alarm, etc.
3.5.2 8 RELAY MODULE OUTPUTS
Form 1 Pole changeover contacts
Voltage-free when unsupervised
Rating ELV only
30V, 2Adc resistive
30V, 1Adc inductive
Operation Programmable
Supervision Programmable 400 Ohm - 10k Ohm
(less than 400 Ohm with series diode)
3.5.3 MAF/PSU OUTPUTS
Brigade Relays
Number/Type 4 relays, 1 pole changeover contacts
Standby Normally energised
De-energises on battery fail or panel fail or in program mode.
Fault, Isolated, Normally de-energised
Alarm Energise on active state
Rating ELV only
30V, 5Adc resistive
30V, 3Adc inductive
Isolation 1500V rms contact to coil