8.4 MODULE RELAY RESET SUPERVISION FAULT
8.4.1 FUNCTION
To reset a latched supervision fault on a single module relay or a continuous range of
relays.
Each module relay may be programmed to be latching/non latching and mapped/not
mapped to the MAF.
If a module relay is programmed as latching then when a supervision fault occurs the
relay will remain latched in fault after the supervision fault is physically cleared.
To reset a latched fault on a module relay a reset command is used.
For network systems, to reset a relay on a remote panel use a zone reset command -
refer to Section 11.10.
8.4.2 OPERATING SEQUENCE
To reset a local module relay, from the base display press:
to select module relays
then press either:
to reset relay nn
or:
to reset the range of relays nn to mm inclusive. You will be prompted to press "ACK" to
confirm the reset or press "CLEAR ESC" to abort.
If the fault is still physically present on the relay then the relay will remain latched in fault.